Presented at the 21ST ANNUAL AIVC CONFERENCE
The Hague, Netherlands, 26 -29 September 2000.
Ventilation in US Manufactured Homes:
Requirements, Issues and Recommendations
Michael Lubliner, Andrew Gordon
Washington State University Extension Energy Program
SYNOPSIS: US
Manufactured homes are required to be built to Department of
Housing and Urban Development's Manufactured
Home Construction and Safety Standards (MHCSS.) The National Fire
Protection Association recently updated ventilation standards
for manufactured homes (NFPA501-1999.) HUD will review and consider
adopting the NFPA501-1999 ventilation standards for their revisions
to the MHCSS. Both the NFPA and HUD standards process received
input from staff involved with energy efficient manufactured housing
programs such as The Super Good Cents™/Natural Choice™
program (SGC/NC), USDOE Building America Industrialised
Housing Partnership (BAIHP), and EPA's Energy Star program. Members
of ASHRAE and the National Institute of Standards and Technology
(NIST) provided contributions as well. NIST and Forest Products
Lab provided HUD with research assistance on the 1994 revisions
to the MHCSS ventilation standards (Burch/TenWolde.) In
1999, HUD requested that NIST conduct CONTAM modeling research
to evaluate ventilation requirements for the future revisions
to MHCSS (Persily.)
The modeling found
that:
- The assumption
of 0.25 air changes per hour (h-1) for infiltration
is problematic given the dynamics of infiltration.
- Operation of
kitchen or two bath fans typically increases ventilation rates
to 0.7 h-1.
- Forced air-system
duct leakage typically increases infiltration rates to 0.55
h-1.
- Exhaust fans
and supply duct leakage draw moisture into the home in hot humid
climates.
- Energy use and
duct leakage of ventilation systems connected to forced-air
systems is considerable.
- Passive inlet
window vents provide little improvement in ventilation effectiveness.
- Exhaust fan location
has little impact on ventilation rates, outdoor air distribution
or home pressures.
- Improved control
strategies are needed to reduce energy use and improve ventilation
effectiveness.
- Additional CONTAM
research is needed on pollutant exposures, parametric studies,
windows and controls.
- There is a need
to perform in-situ field data collection to validate the modeling
conclusions.
The
following author recommendations were provided to both NFPA and
HUD and are based on experiences from the construction of over
90,000 SGC/NC and BAIHP energy efficient manufactured homes,
and on the NIST research findings:
- Controls to optimize
air change rates and minimum energy cost should be considered.
- Use envelope
and ductwork fan pressurization and ventilation system flow
rate testing.
- Tighten floors,
ceilings and ductwork to prescribed levels.
- Utilize air inlets
only when needed.
- Combine whole
house and bathroom exhaust fans when ductwork, undercut doors
or grills connect rooms together.
- Define de-pressure
limits that minimize fireplace back-drafting and moisture condensation
problems.
- Consider the
impact of kitchen and bathroom exhaust fan damper leakage on
reducing pressure imbalances and distribution of outside air.
- Use quiet, durable
and energy efficient ventilation fans.
- Educate occupants
on operation of ventilation system using homeowner manual, labels,
brochures and videos.
1.0
HUD - MHCSS:
Overview: In the United States, 15-20% (200-300,00) of
new single family dwellings are built in manufactured housing
plants. These homes are usually built in 1-3 sections and transported
up to 500 km (300 miles) to a site where the axles and wheels
are removed and the sections connected.
Gaskets and/or caulking are used to seal the ceiling, floor and
wall "marriage-line". A 6m (20 ft), 30 cm (12 in) diameter
insulated plastic flexible "crossover duct" in a vented
crawlspace connects to the HVAC ductwork located below the floor
and above the floor insulation in the "belly."
The construction and installation of these manufactured homes
must meet requirements contained in the U.S. Department of Housing
and Urban Development's (HUD) Manufactured Home Construction Safety
Standards (MHCSS.) MHCSS address structural, fire safety, energy
efficiency issues, and has requirements for providing outdoor
air ventilation. MHCSS supersedes local and state building codes.
HUD provides interpretive bulletins to MHCSS.
1.1 MHCSS
1994 Requirements and Issues: The
requirements and relevant issues to the 1994 revisions to MHCSS
(MHCSS94) are as follows:
- Occupant Control: MHCSS requires an occupant controlled
whole house ventilation system. The typical system uses an
outside air duct to the return side of the forced-air system
which brings in 63 -104 l/s (30-50ft3/min)
on thermostat demand or when the occupant turns the thermostat
fan switch from "auto" to "on". Experience
has shown that these systems tend to only operate in thermostat
demand mode, and are rarely used by occupants for supplemental
ventilation. Some occupants perceive these systems as noisy,
uncomfortable, and wasteful of energy (Lubliner.)
- Flow Rates:
MHCSS94 requires that whole house ventilation systems be capable
of providing .0068 l/s/m2 (0.035 ft3/min/ft2.)
However, MHCSS does not require flow rate testing to ensure
adequate flow rate compliance as part of a quality assurance
program (Lubliner.)
- Infiltration
Assumption: The MHCSS94 requires a flow rate of .0068 l/s/m2
(0.035 ft3/min/ft2.) This requirement
assumes a 0.25 h-1 from infiltration as a single
value for weather-driven infiltration rates. This approach is
inherently problematic, given the strong dependence of infiltration
on weather (Persily.)
- Balanced Ventilation: MHCSS requires systems be "balanced", but provides
no quantifiable definition of "balanced". Perfect
balancing cannot be achieved due to building envelope, HVAC,
occupants and weather dynamics (Lubliner.)
- Pressure Relief: Originally, the MHCSS94 required
pressure relief vents for forced-air intake systems because
of concerns about "positive pressure."
In fact, field tests confirm that supply duct leakage creates
negative, not positive pressure whenever the forced-air system
operates (FSEC, Palmiter.) This is clearly due to the
presence of supply ductwork leakage and lack of return ductwork
outside the building pressure envelope. MHCSS94 no longer requires
"pressure relief" vents in cases where kitchen and
bathroom exhaust fan damper leakage is shown to reduce pressure
imbalances. Many of the industry standard bathroom and kitchen
exhaust fans provide sufficient pressure relief, provided they
are used as intermittent spot ventilation devices. Dampers
around standard industry bath fans have Equivalent Leakage
Areas (ELAs) comparable to the outside air intake forced-air
systems and greater than window air inlet vents (Lubliner.)
- Outside Air
Source: MHCSS94 also states that the ventilation system
cannot draw or expel air into the floor, wall, or ceiling/roof
systems, even if those systems are vented. In reality, when
HVAC equipment operates, most outside air enters through leakage
in the building envelope, kitchen and bath exhaust fan dampers,
as well as leaks in the duct system, rather than the ducted
vents or window inlets. To address this requirement, HUD required
air inlet vents for whole house exhaust systems, unless it
is shown that kitchen or bath fans damper leakage provide air
intake comparable to that of the window inlet vents. Just like
the
"pressure relief vents," the initial requirement
for additional air intake window vents or vents to the air-handler
return ductwork provided little benefit based on the ratio
of envelope ELA to air inlet vent ELA for typical envelope
tightness levels.
- Outside Air
Forced-air Approaches: One approach uses no damper. This
allows conditioned air to exfiltrate when the HVAC is not operating
and increases HVAC distribution system cycling losses. When
the forced air system operates, the intake acts like a 12.5
cm (5inch) diameter leak in return ductwork. The other approach
uses a motorized damper in the air intake duct that opens whenever
the forced-air system fan operates. This approach avoids the
exfiltration cycling losses, but still acts like a supply ductwork
leak whenever the forced-air system operates.
- Location of
Whole House Exhaust Fan: MHCSS94 states that the bathroom
fan can not be used as the whole house fan. Because of the increased
costs of adding the additional fan, most manufacturers utilize
one of the two forced-air ventilation system approaches instead
of the exhaust system. Those that do use a whole house exhaust
fan are permitted to use a noisy, inexpensive bath fan, which
are typically not designed for continuous durable operation.
Since rooms in manufactured homes are typically connected by
ductwork, undercut doors and transom grills, spatial ventilation
effectiveness is adequate regardless of the location of the
whole house exhaust fan.
2.0 NFPA
Standard 501: The NFPA Manufactured Homes Technical Committee
on Mechanical recently reviewed and updated Standard 501. Upon
receipt HUD will consider adopting the new NFPA501-1999 as an
updated MHCSS. The new proposed standard will receive public comment
prior to adoption.
2.1 Improvements
to NFPA Standard 501: NFPA501-1999 made progress in addressing
many of the issues arising from the MHCSS94 including:
- Requiring more
specific design, installation and material details for controlling
building envelope and ductwork air leakage.
- Improving occupant
education and labeling efforts for whole house ventilation systems.
- Requiring quieter
and more durable whole house exhaust fans.
- Limiting the
differential pressure caused by whole house ventilation systems
to no more than 7.0 Pa (.028 in. H2O)
- Allowing the
whole house fan to be installed in the bathroom, provided that
the room is connected by ductwork to the other zones of the
house. It is expected that the cost savings of locating the
whole house fan in the bathroom will be used to purchase quieter
and more durable fans, improved controls, better occupant education
and labeling efforts.
2.2 Outstanding
Issues of NFPA 501 Draft: While the NFPA501-1999 improves
the MHCSS94, NFPA501-1999 did not accept the following recommendations
provided by committee members and building scientists during the
NFPA standards process (NFPA Draft):
- Periodic envelope
and duct performance leakage tests using blower doors and duct
blasters to fully address the problems encountered with envelope
and duct leakage as a result of inadequate practices and materials
in both manufacture and installation.
- Address the increased
energy impacts of the forced-air based ventilation systems (a
350W fan motor which supplies 63-104 l/s (30-50 ft3/min)
of outside air,) and the duct leakage energy penalties from
distributing that air through the HVAC supply ductwork.
- Eliminate window
and return duct inlet vent requirements, except where manufactured
homes are tight enough to warrant their use. Eliminating the
inlet vents provides cost savings, which can be used to limit
floor, ceiling and duct leakage. The current predominant vehicle
for intake air in whole house exhaust systems is the building
envelope. Given current envelope and duct tightness levels,
eliminating inlet vents will have little effect on the amount
of airside air which is drawn in thorough the envelope. Figure
A provides the results of house tightness on manufactured homes
throughout the USA, and indicates that homes are not achieving
desired tightness levels where inlet vents are in use. Focusing
on sealing penetrations in floors, ceiling and ductwork where
known pollutant sources may enter may be a more effective way
to reduce outside air being drawn from the crawlspace and attic.
Outside air drawn through wall envelope penetrations may increase
the drying potential of homes in heating climates (Lstiburek),
and may filter pollen better than air inlet vents. More discussion
and research is needed to determine how different ventilation
systems effect pollutant sources and emission rates, since some
pollutant sources may increase while others decrease. In addition,
some researchers suggest that some heat recovery occurs when
outside air is drawn through walls (Nelson.)
3.0 ASHRAE
Standard 62.2: Concurrent with the NFPA501 revisions, the
American Society of Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE) produced residential Standard 62.2,
"Ventilation for acceptable indoor air quality." Both
ASHRAE 62.2 and NFPA501 are fairly consistent in terms of requirements,
although the approaches vary. Some of the ASHRAE 62.2 committee
members provided useful comments to the NFPA501 development,
review, and comment processes (NFPA Draft.)
4.0 SGC/NC: Significant
input to the ASHRAE 62.2 and NFPA 501-2000 standards processes
came from lessons learned from the U.S. Northwest region's
Super Good Cents™/Natural Choice™/Energy Star (SGC)
energy efficiency construction program for manufactured homes.
The SGC program has resulted in the construction of 90,000 energy
efficient homes over a ten-year period.
4.1 SGC
Specifications Versus MHCSS94: SGC does not allow forced-air fans to be used
as the whole house ventilation systems, thereby avoiding parasitic
energy losses from the forced-air fans. In cooling climates these
losses increase cooling loads, while in heating climates they
offset some heating load.
- SGC requires
quieter (1.0 - 1.5 sone) whole house exhaust fans.
- SGC employs periodic
in-plant and in-field random performance testing of building
and duct tightness, and is working on improved duct sealing
and installation techniques that employ mastics and gaskets
instead of tapes.
- SGC has effective
occupant education brochures and labeling materials to help
occupants understand their ventilation system and the importance
of operation during occupancy periods.
- Existing
and Future SGC/NC Specification
Fan Noise and
Operation: The SGC program requires a 1.0 sone fan running
constantly or a 1.5 sone fan set to run for at least 8 hours per
day during occupancy periods. A proposal to eliminate the 1.5
sone fan option has been approved, along with improvements to
the occupant ventilation brochure, suggesting operation of the
system whenever the home is occupied.
Inlet Vents via window frames or return ductwork: Another
requirement is either air inlet window vents in each bedroom and
one in the main living area, or ducted intake to allow some outside
air to enter when the whole house exhaust fan runs, regardless
of the forced-air fan operation. There are two ducted intake air
systems: one uses a motorized damper that only opens when the
whole house exhaust fan is operating. This system, called the
"Northwest Timer kit" cycles the whole house exhaust
fan on for 20 minute per hour. The other system has no damper
and acts like a return duct leak, increasing cycling losses as
described above in the discussion of MHSCC. A proposal to eliminate
requiring inlet vents, focussing on tighter ducts and floor/ceiling
envelopes has been approved by SGC manufacturers.
5.0 DOE
BAIHP: The US
Department of Energy's (DOE) Building America Industrialised
Housing Partnership (BAIHP) is providing building science training,
testing, and general technical assistance to manufacturers throughout
the USA. This includes monitoring of energy use, indoor air quality
and HVAC system performance. Current BAIHP activities include:
Moisture Investigations:
Testing of standard practice and energy efficient manufactured
homes in the warm humid Southeast USA have found mold due to condensation
behind vinyl-covered drywall, primarily due to a combination of
air infiltration from HVAC induced negative house pressures (cause
by supply duct leakage), and cold-side vapor barriers.
BAIHP is focusing on cost effective ways of tightening supply
ductwork to reduce moisture condensation on cold side vapor barriers
(vinyl-covered drywall) in hot humid climates. Tightening ducts/building
envelopes and eliminating cold side vapor barriers seems to be
effective in reducing moisture condensation problems (FSEC.)
Combustion spillage: FMCSS
requires that combustion air be supplied directly from outside.
However, some wood fireplaces with loose operable access doors
have been observed "back-drafting" smoke into the homes
under excess negative pressures caused by the HVAC equipment (Boe.)
BAIHP is investigating the frequency of back-drafting occurrences
in SGC/NC homes in the Pacific Northwest.
Ventilation Controls: BAIHP
also helped to develop a new control called the Air Recycler
. This controller adjusts the ventilation rate based on operational
time of the furnace and occupancy level (Rudd.) The Air
Recycler has had limited use in manufactured housing. One
concern is that it typically relies on the operation of an inefficient
furnace fan for ventilation. Suggestions to overcoming this problem
include the use of a low-wattage whole house exhaust fan instead
of the forced-air fan (Lubliner.) Another solution is to
use a variable speed high efficiency fan motor; this may be first-cost
prohibitive to an industry that typically pays less than $200
for an electric forced-air furnace. NIST and WSU are currently
developing a new control system, which would adjust the ventilation
system run-time based on an estimate of the infiltration rate.
Performance Monitoring:
BAIHP is monitoring the energy and HVAC performance in new current
practice and energy efficient manufactured homes in the US. The
monitoring results are helping to support recommendations to improve
ventilation system performance.
Energy Star Technical
Assistance: BAIHP staff provide field testing and other technical
assistance to manufacturers interested in building homes to the
Energy Star Manufactured Home program standards. Energy Star homes
are built 30-50% more efficient than current practice. Energy
Star is currently working on energy efficient ventilation specifications,
and recognizes energy savings in SGC manufactured homes associated
with low wattage exhaust ventilation systems (EPA.)
6.0 HUD/NIST/CONTAM: In 1999, HUD directed NIST to employ CONTAM, a multi-zone
airflow and indoor air quality computer program, to simulate airflow
in a 99 m2 (1063 ft2) double-section home
under several different scenarios. These scenarios included envelope
infiltration only, infiltration plus the effects of local exhaust
and forced-fan operation, an outdoor air intake duct installed
on the forced-air return, and whole house exhaust with and without
passive inlet vents. Simulations were performed to predict outdoor
ventilation rates into the house due to infiltration and mechanical
ventilation, inter-zone airflow rates between the rooms, building
air pressures, and ventilation air distribution.
6.1 Summary
of findings
Validity
of the 0.25 h-1 assumption for infiltration: Using
a single value for a weather-driven infiltration model is inherently
problematic, given the strong dependence of infiltration on weather.
Infiltration rates vary by as much as 5:1 in these simulations,
based on weather conditions alone. Impacts of the exhaust fan
and forced-air system more than double these variations. Nonetheless,
when considering predicated infiltration rates on an annual basis,
the air change rate is below 0.25 h-1 for about one-third
of the year in Albany, NY and Seattle, WA, and for 70% of the
year in Miami, FL. Note that if there were no duct leakage in
these homes, these percentages would be significantly higher.
The assumption of 0.25 h-1 in modern manufactured homes
may be high; more importantly, it ignores the variation due to
weather and HVAC operation (see Figures B1
and B2.)
Impact
and effectiveness of outdoor air inlets on the force-air return
ductwork: Employing an outdoor air intake on the forced-air
return duct is effective in raising air change rates and distributing
ventilation air throughout the home. However, the overall impact
on the home's air change per hour is a function of the operating
time of the forced-air system, which in turn depends on the extent
of system over-sizing and the use of other control strategies,
such as manual switches and timers. While increased forced-fan
operation provides higher ventilation rates, there is an energy
cost associated with increased fan operation. Also given the
existence of significant duct leakage, this scenario creates
excessive air change rates, particularly when weather-driven
infiltration is high (see Figures B1, B2,
and D.)
Impact
and effectiveness of whole house exhaust fan with and without
passive inlet window vents: A whole house exhaust fan with
passive inlet vents provides adequate ventilation and reasonable
distribution, but again is highly dependent on the fan operation
schedule. As implemented in the house model, these vents themselves
are not particularly effective in ventilating the home. Based
on the magnitude of the vent openings relative to house tightness,
their installation basically corresponds to a 15% leakier envelope
than a designed air intake system. Such a system would presumably
require a tighter envelope than is typically achieved in practice.
Furthermore, under the conditions in these simulations, outdoor
air did not necessarily enter the building through these vents;
when they did indeed act as inlets, the amount of outdoor air
entering through them was not significant (see Figures B1,
B2, and C.)
Locating the
whole house exhaust fan in the main living area versus the bathroom:
In this model, the impact of the whole house fan did not greatly
depend on its location. Whether the fan was in the main living
area or a bathroom off the main living area did not have a significant
impact on the air changes per hour, outdoor distribution or building
pressure (see Figure C.)
7.0 Recommendations: Key recommendations for MHCSS include:
- Consider system
design and control impacts on ventilation effectiveness and
energy use.
- Utilize fan/duct
pressurization testing for quality assurance.
- Conduct flow
rate testing for quality assurance.
- Improve occupant
education and labeling efforts.
- Define de-pressure
limits to minimize back-drafting in heating climates.
- Consider how
kitchen and bathroom fan leakage may reduce negative pressure
and impact distribution of outside air.
- Define de-pressure
and perm rating limits, tighten ductwork and building envelope
and prohibit cold side vapor barriers to minimize moisture condensation
in hot humid climates.
- Define de-pressure
limits or improve systems to reduce back-drafting of fireplaces
with leaky doors.
- Require quiet,
durable and energy efficient ventilation fans, and improve occupant
use of systems through education.
- Eliminate the
requirements for outside air intakes on exhaust systems in heating
climates and use cost savings to tighten floors, ceilings and
ducts.
- Allow whole house
fans to be located in bathrooms, provided the bathroom is connected
to the house by ductwork, undercut doors or grills.
- Conduct additional
CONTAM research, including pollutant modeling, parametric studies
on key variables and operable window impacts. After CONTAM modeling,
validate assumptions and results through field research.
8.0 Figures
Figure A - House Tightness Research
Figure B-1 - Summary of Annual ACH during
occupancy
Figure B-2 - Summary of Annual ACH at
Heating and Cooling
Figure C- Summary of Inverse Age of Air
Values
Figure D - Summary of Energy Consumption
and ACH
9.0 Acknowledgements:
The CONTAM work was performed under an interagency agreement
between NIST and HUD. The paper was developed with support from
the DOE Building America Industrialised Housing Program. The authors
acknowledge the support of Andrew Persily at NIST. The following
persons provided additional input and assistance: Subrato Chandra
and Neil Moyer at FSEC, William Freeborne and John Stevens at
HUD, George James at DOE, David Baylon, Larry Palmiter, and Bob
Davis at Ecotope Inc. Paul Zigler at National Conference of States
on Building Codes and Standards, Joe Lstiburek and Armin Rudd
of Building Science Corporation, Gary Nelson of the Energy Conservatory,
Don Stevens at HVI, Mike Zieman at RADCO, Anton TenWolde at Forest
Products Laboratory, and Bob Lorenzon and Ann Porterfield of the
Eugene Water and Electric Board.
10.0 - References
Alternative Energy Corporation. Air of Importance.
A Study of Air Distribution Systems in Manufactured Homes.
1996.
ASHRAE. ANSI/ASHRAE Standard 62-1999, Ventilation for
acceptable indoor air quality. 1999.
ASHRAE. ASHRAE Handbook Fundamentals, Chapter 25 Ventilation
and Infiltration. 1997.
ASHRAE. ANSI/ASHRAE Standard 136-1993, A method of
determining air change rates in detached dwellings. 1993.
ASHRAE. ANSI/ASHRAE Standard 119-1988, Air leakage
performance for detached single-family residential buildings.
1988.
ASTM. E779-87, Standard test method for determining
air leakage rate by fan pressurization. 1987.
ASTM. E1827-96, Standard test method for determining
airtightness of buildings using an orifice blower door. 1996.
Baylon, D., Davis B., and Palmiter, L. Manufactured
Home Acquisition Program. Analysis of Program Impacts. Ecotope,
Inc. 1995.
Boe. A.B. Field observations from SGC/NC homes in Oregon.
Oregon State University Energy Extension Program. 1997-99.
Chandra, C., Beal, D., and McKendry, B. Energy efficiency
and indoor air quality in manufactured housing. Affordable
Comfort 98 Selected Readings. 1991.
Cummings, J.B., Tooley, J.J. Jr., and Moyer, N. Investigation
of Air Distribution System Leakage and Its Impact on Central Florida
Homes. Florida Solar Energy Center, FSEC-CR-397-91. 1991.
Cummings, J.B., and Tooley, J.J. Jr. Infiltration and
pressure differences induced by forced air systems in Florida
residences. ASHRAE Transactions, 95 (2), pp. 551-560. 1989.
Davis, B., Siegel, J., Palmiter, L., and Baylon, D. Field
Measurements of Heating System Efficiency in Nine Electrically-Heated
Manufactured Homes. Ecotope, Inc. 1996.
EPA. Letter to Tom Eckman at Northwest Power Planning
Council regarding SGC/NC equivalency to Energy Star. September,
1999.
Hadley, D.L. and Bailey, S.A. Infiltration/Ventilation
Measurements in Manufactured Houses - Residential Construction
Demonstration Program. Pacific Northwest Laboratory, PNL-7494.
1990.
HUD-MHCSS. Manufactured Home Construction and Safety
Standards, Part 3280. U.S. Department of Housing and Urban
Development. 1994.
Lstiburek. J. Comments made in response to question posed
during the Energy Efficient Building Association. Conference panel
session on ventilation systems. 1999.
Lubliner, M., Stevens, D.T., and Davis, B. Mechanical
ventilation in HUD-code manufactured housing in the Pacific Northwest.
ASHRAE Transactions, 103 (1), pp. 693-705. 1997.
Moyer, N. Moisture Problems in Manufactured Housing
in Hot Humid Climates. Presentation at February 2000 meeting
at Florida Solar Energy Center of the USDOE's Building America
Industrialised Housing Partnership program.
Nelson, G. Conversation with M. Lubliner et. al. at ASHRAE
Annual 2000 meeting.
NFPA501. NFPA501, Standard on Manufactured Housing.
National Fire Protection Association. 1997.
NFPA501. Comments submitted by Lubliner, Heiman, Sherman,
and TenWolde regarding draft NFPA501 standards. National Fire
Protection Association. 1999.
Palmiter, L.S.; I.A. Brown, I.A., and Bond, T.C. Measured
infiltration and ventilation in 472 all-electric homes. ASHRAE
Transactions, 97 (2), pp. 979-987. 1997.
Palmiter, L.S., Bond, T., Brown, I.A., and Baylon, D.
Measured Infiltration and Ventilation in Manufactured Homes.
Ecotope, Inc. 1992.
Persily, A.K. A Modeling Study of Ventilation in Manufactured
Homes. National Institute of Standards and Technology, NISTIR
6455. 2000.
Rudd, A. Air
RecyclerÔ
Control Installation manual. 1999.
SGC. Super Good Cents Specifications. Oregon Office
of Energy. 1996. TenWolde, A. and Burch, D.M. Ventilation, Moisture
Control, and Indoor Air Quality in Manufactured Houses. Forest
Products Laboratory, National Institute of Standards and Technology.
1996. |