|
|
|
Reference
Publication:
Chandra, Subrato, Neil Moyer, Danny Parker, David Beal,
David Chasar, Eric Martin, Janet McIlvaine, Ross McCluney,
Andrew Gordon, Mike Lubliner, Mike McSorley, Ken Fonorow,
Mike Mullens, Mark McGinley, Stephanie Hutchinson, David
Hoak, and Linda Tozer. Building America Industrialized
Housing Partnership, Annual Report - Fourth Budget Period.
04/01/03-03/31/04. |
|
|
Building
America Industrialized Housing Partnership, Annual
Report - Fourth Budget Period |
|
|
Subrato
Chandra, Neil
Moyer, Danny
Parker, David
Beal, David
Chasar, Eric
Martin, Janet
McIlvaine, Ross
McCluney, Andrew
Gordon, Mike
Lubliner, Mike McSorley, Ken
Fonorow, Mike
Mullens, Mark
McGinley, Stephanie
Hutchinson, David
Hoak, and Linda Tozer |
|
Florida
Solar Energy Center |
|
|
|
Building
America Industrialized Housing Partnership (BAIHP)
TRIP
REPORT
Southern
Mississippi
Problem
Home Inspection, Testing and Possible Solutions
DATE
August
9, 2001
PURPOSE
- Assist
service and engineering staff in determining the
source or probable cause of moisture-related problems
and aid in repairs.
- Provide
confirmation, if possible, that moisture related
problems would not reappear.
INTRODUCTION
- Moisture
problems included some discoloring of wallboard and
staining of ceiling trim at various transitions. Also, a
section of wallboard near the front door had deteriorated
from water intrusion.
- Previously
damaged wallboard had been replaced once already
by service personnel. Repairs included replacing
with damage drywall with a similar product, repairing
supply duct system leakage and sealing wall-ceiling
penetrations.
DESCRIPTION
- 3
bedroom-2 bath 1330 ft2 singlewide with
fireplace.
- Open
crawlspace without skirting
- 3 ½ ton
split system AC and electric strip heat furnace
with an in-line metal floor duct system with metal
risers.
OBSERVATIONS
- Thermostat
was set at 75F
- Repairs
previously made included wallboard replacement, duct
sealing (with mastic), and sealing of various ceiling
transitions.
- Blend-Air
II ventilation system installed. The attic ventilation
fan had been disconnected.
- Homeowner
reported that the electric bill for the summer decreased
by $40 after the repairs were made.
- All
bedroom doors usually closed at night and open during
the day.
- Occupants
include 2 adults, 2 teenagers and 4 pets (2-cats and
2 dogs).
TESTING
Blower
door test
A
blower door test was done to determine the airtightness
of the building envelope. A series of building
pressures and associated airflows was recorded. This
provides the necessary inputs to determine the CFM50
of the house. As a general rule of thumb, typical
values of building airtightness range between 0.75 and
1 CFM50 per square foot of conditioned floor area. This
house has a floor area of 1216 ft2 and a CFM50
of 1855 or 0.7 CFM50 per square foot – a tighter
home.
Blower
Door Test –As Found
CFM50
= 1855
[C=163.1,
n=0.62, r=0.99] |
The
values of C and n can be used as inputs for the house
airflow equation, Q=C* pn. Thus, for
any given pressure difference, P, the airflow crossing
the building’s envelope can be determined.
Duct
test
A
duct system airtightness test was also completed. A
duct tester was attached to the air handler unit. The
supply registers were temporarily sealed off and the
system was then depressurized to 25 pascals. The
total and outside leakage flow components were measured. An
airtight duct system would have zero leakage or both
the CFM25total and CFM25out would
be 0.
Duct
System Airtightness |
CFM25total =
47
CFM25out =
32 |
Pressure
diagnostic testing
Pressure
differential measurements were completed to determine
a magnitude and direction of flow across the envelope
when the air handler fan operates. Interior door
closure effect was also measured when the air handler
fan operated.
Pressure
Diagnostics w/ AHU
(Note:
the winds were calm) |
Condition |
Pressure
differential (main wrt outside) |
All
fans off |
0
pa |
AHU
on |
-1.6
pa |
AHU
on & master suite door closed |
-10.7
pa |
AHU
on & all interior doors closed |
-13.0
pa |
The
pressure difference was also measured across each closed
door when the air handler fan was operating (all supply
registers were open and exhaust was off).
Pressure
across closed doors |
Pressure
differential (room wrt main) |
Master
bedroom |
24.5
pa |
Center
Bedroom |
3.9
pa |
End
Bedroom |
6.6
pa |
EFFECTS
- Return
air path to AHU is hindered when bedroom doors are
closed – especially
the master suite door.
- Flow
imbalances cause the master bedroom to be overcooled
before the other bedrooms are cooled. This overcooling
causes the exterior vinyl covered walls to drop to the
ambient air dewpoint temperature or below.
- Duct
leakage, on the supply side, causes the entire building
to operate at a negative pressure. Any pathway
from the exterior to the interior – such as electrical
penetrations- provides a pathway for ambient air to reach
interior surfaces. One such area is at the light
fixture mounted on the wall of the master bath.
RECOMMENDATIONS
- Keep
thermostat set at 78 F or above.
- The
flow imbalances (especially the excessive air in
the master suite) should be corrected.
- All
duct leaks should be repaired with mastic. The
supply plenum and all risers should be checked and repaired
as needed. The refrigerant line penetration through
the air handler cabinet should also be sealed. The
duct leakage should not exceed 3% of floor area or CFM25
less than 40.
- The
3-inch reducer in the supply plenum should be removed.
- A
separate return direct to the AHU is needed (through
the wall or jump duct) from the master suite.
- Sufficient
return air pathways should be installed in the rest
of the bedrooms.
- All
belly penetrations should be sealed with a permanent,
long-lasting seal. No duct tape.
- In
general, vinyl covered exterior drywall should not
be used in hot and humid climates.
PICTURES
|
|
Front
elevation |
Rear
elevation |
|
|
Compliance
sticker |
Blower
door assembly |
|
|
Duct
tester attached to furnace |
Thermostat |
|
|
Outside
air duct to furnace top |
Furnace
fan removed to inspect plenum |
|
|
Electric
furnace with 3-row AC coil |
AC
nameplate |
|
|
Ceiling
transition repair being made |
Inspecting
wall moisture content |
|
|
AC
condensate draining on pier and ponding |
Eroded
pier support under hall bath |
|
Close-up eroded
pier support |
|
Disclaimer:
This report was prepared as an account of work sponsored by an agency
of the United States government. Neither the United States government
nor any agency thereof, nor any of their employees, makes any
warranty, express or implied, or assumes any legal liability
or responsibility for the accuracy, completeness, or usefulness
of any information, apparatus, product, or process disclosed,
or represents that its use would not infringe privately owned
rights. Reference herein to any specific commercial product,
process, or service by trade name, trademark, manufacturer,
or otherwise does not necessarily constitute or imply its endorsement,
recommendation, or favoring by the United States government
or any agency thereof. The views and opinions of authors expressed
herein do not necessarily state or reflect those of the United
States government or any agency thereof.
|