|
|
|
Reference
Publication:
Chandra, Subrato, Neil Moyer, Danny Parker, David Beal,
David Chasar, Eric Martin, Janet McIlvaine, Ross McCluney,
Andrew Gordon, Mike Lubliner, Mike McSorley, Ken Fonorow,
Mike Mullens, Mark McGinley, Stephanie Hutchinson, David
Hoak, and Linda Tozer. Building America Industrialized
Housing Partnership, Annual Report - Fourth Budget Period.
04/01/03-03/31/04. |
|
|
Building
America Industrialized Housing Partnership, Annual
Report - Fourth Budget Period |
|
|
Subrato
Chandra, Neil
Moyer, Danny
Parker, David
Beal, David
Chasar, Eric
Martin, Janet
McIlvaine, Ross
McCluney, Andrew
Gordon, Mike
Lubliner, Mike McSorley, Ken
Fonorow, Mike
Mullens, Mark
McGinley, Stephanie
Hutchinson, David
Hoak, and Linda Tozer |
|
Florida
Solar Energy Center |
|
|
|
Building
America Industrialized Housing Partnership
TRIP
REPORT
Southeast
Texas – 8/21/01
Energy Star, Manufactured Home Certification
DATE
September
18, 2001
ATTENDEES
David
Chasar, Bob Abernethy - FSEC
PURPOSE
- Audit
and test home to determine Energy Star certification.
- Verify
compliance with Energy Star Manufactured Home Site
Installation Checklist.
DESCRIPTION
- 4Bd
/ 3Ba home with 2,356 Sq Ft conditioned floor area
- Crawlspace
was not skirted in the traditional fashion – siding
installed to ground level
- Ground
cover – monolithic concrete slab throughout crawlspace
(see picture)
- Ducts
are located in the attic including the crossover connection
- 4
ton Nordyne heat pump (12 SEER / 7.6 HSPF)
- Ventilation
provided by whole house exhaust fan
- Water
heater is a Seisco tank-less instant hot water unit
OBSERVATIONS
- The
home passed all Energy Star certification guidelines
- Two
porches were added to the South and West sides providing
10 foot overhangs for those windows
- No
significant belly tears were found during a crawlspace
inspection however pressure diagnostics showed the
belly zone to be in much better communication with
ambient air than with the inside of the home.
- HERS
score – 88.6 (obtained with Energy Gauge USA
v1.24)
TESTING
Blower
door test
A
blower door test was done to determine the airtightness
of the building envelope. A series of building pressures
and associated airflows was recorded. This provides
the necessary inputs to determine the CFM50 of the house. The
ACH50 and natural air infiltration rate (ACHnat) were calculated
from site-specific information about the home (volume,
climate, etc).
Blower
Door Test
ACH50 = 6.26
ACHnat = 0.27
CFM50 = 2132
[C=188, n=0.62, r=0.996] |
The values of C and n can be used as inputs for the house
airflow equation, Q=C* Pn . Thus, for
any given pressure difference, P, the airflow crossing
the building’s envelope can be determined.
In addition to the standard blower door test, pressure
differentials were measured across the marriage wall and
belly planes with respect to the building interior. These
were taken to determine the relative connection of these
areas to the ambient environment. With the house depressurized
to 50 pascals, a zone well-connected to the house will
have a low pressure reading approaching zero and one that
communicates more with the outside air will have a higher
reading approaching 50.
Marriage
Wall & Belly Zone Test |
Location |
Pressure
differential (zone wrt main body) |
East
Marriage Wall |
+4.5
pa |
West
Marriage Wall |
+4.5
pa |
Belly
(front side) |
+42
pa |
Belly
(back side) |
+42
pa |
Duct test
A
duct system airtightness test was also completed. A
duct tester was attached to the air handler unit. The
supply registers were temporarily sealed off and the system
was then depressurized to 25 pascals. The total and
outside leakage flow components were measured. The
Qn value was calculated by dividing the CFM25out leakage
by total conditioned floor area.
Duct
System Airtightness |
CFM25total =
115 |
CFM25out =
45
Qn = 0.019 |
Pressure diagnostic testing
Pressure
differential measurements were completed to determine
a magnitude and direction of flow across the envelope
when the air handler fan operates. Interior
door closure effect was also measured when the air handler
fan operated.
Pressure
Diagnostics w/ AHU
(Note:
moderately windy conditions)
|
Condition |
Pressure
differential (main wrt outside) |
All
fans off |
0.0
pa |
AHU
on |
-0.4
pa |
AHU
on & all interior doors closed(except util.) |
-1.1
pa |
The
pressure difference was also measured across each closed
door when the air handler fan was operating (all supply
registers were open and exhaust was off).
Pressure
across closed doors |
Pressure
differential (room wrt main) |
Master
bedroom |
+2.4
pa |
No.
East Bedroom |
+2.0
pa |
So.
East Bedroom |
+1.8
pa |
South
Bedroom |
+2.8
pa |
PICTURES
|
|
Front
elevation |
Crawlspace
with concrete slab |
|
|
West
elevation with porch |
Rear
elevation showing no skirting |
|
Disclaimer:
This report was prepared as an account of work sponsored by an agency
of the United States government. Neither the United States government
nor any agency thereof, nor any of their employees, makes any
warranty, express or implied, or assumes any legal liability
or responsibility for the accuracy, completeness, or usefulness
of any information, apparatus, product, or process disclosed,
or represents that its use would not infringe privately owned
rights. Reference herein to any specific commercial product,
process, or service by trade name, trademark, manufacturer,
or otherwise does not necessarily constitute or imply its endorsement,
recommendation, or favoring by the United States government
or any agency thereof. The views and opinions of authors expressed
herein do not necessarily state or reflect those of the United
States government or any agency thereof.
|