II.
BAIHP Technical Assistance (B-C)
- Bellview
Air
Gainesville, Florida
Florida H.E.R.O. discussed a range of issues with Bellview
Air, including the impact of input data on Manual J equipment
sizing and the air handler location in an effort to improve
indoor air quality, comfort, and energy performance.
The potential benefits of unvented cathedralized roof
systems were also addressed. Construction anticipated
in late 2005.
- Bobek
Building Systems
Oviedo, Florida
|
Figure
7 1800 sq.ft.
Steel
Frame
Residence near Oviedo, Florida. |
BAIHP
conducted a testing visit to new BAIHP partner. Bobek
Building Systems building exclusively with steel frame
and partial panelized construction (Figure 7)
to measure whole house and duct leakage and to evaluate
envelope insulation with IR camera. BAIHP compiled the
results of the testing and sent design recommendations
to the builder.
Table
8 Air Tightness Testing |
Blower Door Test Results |
Duct System Airtightness |
CFM50 = 1693 |
CFM25total = 285 |
ACH50 = 7.05 |
CFM25out = 42 |
C=157.8, n=0.607, r 2=0.999 |
Qn = 2.3% |
Duct testing shows low leakage to out (2.3%) but an excessive
level of total leakage. The ducts are located in the attic
which is largely sealed (essentially unvented) with an insulated
steel panel roof deck. During blower door testing, the attic
space was found to depressurize to 13 pascals while the home
was at -50 pascals, showing the space is better connected
to the conditioned space than to the outside. One known area
of attic leakage to outdoors occurs at the front porch overhang.
The high total duct leakage should be addressed to ensure
proper distribution and mixing. In many cases this is caused
by leakage where the supply register ties into the supply
boot. Supply registers with integral foam seals are recommended
to provide a tight fit at the boot connection and where the
register meets the ceiling surface.
Infrared Imaging
|
Figure
8 Thermal Image
of
Exterior, Steel-framed
Walls
|
The
IR picture in Figure 8 shows a corner, side and
front wall from inside the home. This picture is typical
of IR images from inside the house perimeter. Portions of
the wall shown violet in color reflect an indoor temperature
of approximately 67º. Lighter and brighter colors indicate
higher temperatures. Metal studs and points of joining between
the ceiling and side walls can be seen in orange and light
yellow.
As
can be seen from the IR picture, thermal shorts exist between
the outdoor and interior space. Though the overall differential
between room temperature and stud temperature is relatively
small (5ºF), the cumulative effect may
represent a significant conduction load on the space conditioning
system. Reducing thermal bridging between outside and inside
the home will reduce thermal loading taking place inside
the home. This, in turn, will reduce air conditioning run
times.
BAIHP Recommendations included:
- Sealed supply and return registers to reduce total duct
leakage and improve distribution efficiency
- More attention to sealing the attic space from outdoors
since this is essentially a buffer to the conditioned interior
space. This will also lessen any duct leakage to outdoors.
Additionally,
some method of breaking the thermal short between the stud
and the back of the drywall should be deployed in future
construction efforts. Consideration should be given to
applying foam board, ¾” minimum, between
the stud and the drywall. At a minimum, application of adhesive
backed foam strips applied to the stud prior to drywall installation
should be considered.
- Cambridge
Homes
Orlando, Florida
Category B, 1 Home
Note 100% Energy Star Builder
|
Figure
9 The Augusta,
Cambridge Homes BA Prototype |
This BAIHP partnership resulted in continuation of monitored
field research in the Augusta Building America model (Figure
9) and a control home. See BAIHP Research (Section
III), Site Built Housing Research, Cambridge Homes.
In November 2004, BAIHP participated in a meeting with
this partner to discuss water damage incurred in recently
built homes as a result of the 2004 active hurricane
season. Approximately 12 people took part in the meeting
including BAIHP researchers, and Cambridge Homes design,
construction, and architecture personnel.
Results
of field investigations were shared, and potential solutions
discussed.
During the 4 th budget period in cooperation with the
University of Central Florida Industrial Engineering
Department (UCFIE), FSEC researchers tested four Cardinal
modular homes with the Cardinal sales manager and plant
quality engineer. Initial results found that peak loads
for heating were almost double that for cooling. All
four of the homes had leaky ducts. These leaks accounted
for the largest peak load in the homes, averaging 28%
of the winter peak and 21% of the summer peak.
- Champion
Homes
Washington (state)
Champion
Homes built the first stress skin insulated panel (SIP) manufactured
home now sited in western Washington. The house air tightness
was measured at ACH50=3.55, well below the average numbers
for all homes previously tested in the WSU random home study
(see Northwest Energy Efficient Manufactured Homes). Energy
savings are estimated at 50% greater than a home constructed
to the HUD Code. These results were presented at the 2003
ASHRAE Summer Meeting, authored by Pacific Northwest National
Laboratory (PNNL), with contributions from BAIHP staff.
- City
of Gainesville, Cedar Grove II
Gainesville, Florida
Category B, 139 Homes
Award: HUD award for Innovation in Housing in 2004
|
Figure
10 City of Gainesville
house in Cedar Grove II |
Florida
H.E.R.O. began working with the City of Gainesville before
the ground-breaking in the Cedar Grove II subdivision of
HUD housing. Project manager Judy Raymond envisioned a
new urban style development (HUD’s first) with
single family homes featuring high quality construction
and individualized character with front porches and front
façade details (Figure 10). She worked
with Florida H.E.R.O. to develop engineered plans for
mechanical and air distribution systems and a whole house
package that was recognized with a HUD award in 2004. Table
9 summarizes the specifications.
Table
9 City of Gainesville, Cedar Grove II Subdivision,
HUD Home |
Component |
Specification |
Conditioned Area |
~1200-1400 (139 units) |
HERS Rating |
86-88 (goal = 86) |
Cooling And Heating |
SEER 12 with hydronic heating;
some 80% AFUE furnaces with programmable thermostat. |
Duct System |
Ducts in conditioned space.
Ducts moved to attic in later phase. Return duct and
air handler still conditioned space.
Duct system engineered
using Manual D, sealed with mastic, all homes performance
tested for duct air tightness. CFM25 out≈25
|
System Capacity |
Cooling and heating systems
sized using Manual J calculation procedure |
Walls |
R-13 cellulose |
Ceiling |
R-30 cellulose insulation
with radiant barrier |
Windows |
Double pane metal frame |
- City
of Orlando, The Orlando House
Orlando, Florida
Category A, 1 House
|
Figure
11 The Orlando
House |
The
City of Orlando, through the office of Housing and Community
Development in the Planning and Development Department,
constructed an environmentally friendly demonstration home
called The Orlando House: Florida’s
Future, on an infill site within the city (Figure
11). The City requested FSEC assistance to assure
the home met Building America goals and the Florida Green
Home Designation Standards. Ground broke on the demonstration
home in December 2001 and the home was open to the public
for community education purposes for approximately one
year. Specifications are listed in Table 10.
The City acquired more than $100,000 in donated materials
and services for the project, and completed much of the
construction using their own staff. Along with public
education, a primary purpose for this project was to
give the city staff first hand experience in the use
of green building materials and techniques - especially
those relating to energy efficiency, indoor air quality,
durability, disaster mitigation, and termite resistance.
That experience would allow the products and techniques
to be effectively used in future low-income housing constructed
by the city.
Table
10 City of Orlando – Orlando House |
Component |
Specifications |
Conditioned Area |
2148 sq. ft. |
HERS Score |
88.3 |
Envelope |
Above-grade Wall Structure |
Steel Frame 1 st and 2
nd floors |
Above-grade Wall Insulation |
R-19 Icynene |
Exterior Wall and Roof
Sheathing |
OSB - Borate treated |
Attic |
Unvented R-19 Icynene |
Roof |
Metal |
Windows |
Double pane Low-E |
Equipment |
Heating & Cooling |
13 SEER heat pump |
Thermostat |
Programmable |
Ventilation |
Passive outside air vent |
Water Heater |
50 gal, EF=0.88 (Electric) |
Lighting |
100% fluorescent |
Appliances |
Energy Star |
Additional Green
Features:
- Termi-mesh
- Safe Room
- VOC source control
- Resource efficient interior finishes
|
- Durable exterior finishes
- Ultra-low-flow water fixtures
- Low water using landscape
- Pervious driveway/walkway
|
One particular focus of this project was disaster resistance.
For protection from wind storms, a durable steel structure
was used along with a safe room located in the detached
garage. For termite resistance, all structural and exterior
finish materials were selected on the basis of providing
the least amount of available food source. Materials
such as borate treated lumber and sheathing, steel structural
components, and plastic/composite finishes were used
extensively in conjunction with a Termi-mesh barrier
system.
FSEC
certified the house for the Florida Green Home Designation
Standard in February 2003. FSEC staff also presented information
regarding Florida Green Home Designation as part of a builder
training event held at the Orlando House. Two CEUs were
available to attendees, and approx. 30 people attended
from the central Florida area. Training also included talks
on Zero Energy Homes, Florida Sun Built Program, and a “builder panel” that
included 3 BAIHP partner builders.
The demonstration home was sold in May 2003, and money
acquired from the sale will go directly towards the construction
of low income housing that utilizes several green building
techniques.
- City
of Lubbock Community Development
Lubbock, Texas
|
Figure 12 Low income
housing
built
by the City of Lubbock using
insulated
concrete forms.
|
Through the Portland Cement Association (PCA), contact
was established with the City of Lubbock who is building
low income houses with insulated concrete form (ICF)
systems (Figure 12). FSEC researchers visited
Lubbock twice to conduct diagnostic tests and provide
training and technical assistance. FSEC also conducted
initial HERS ratings on four Lubbock Habitat for
Humanity (see Habitat for Humanity, Texas) homes
plans and introduced the Habitat affiliate to the
City of Lubbock’s
other low-income housing activities.
- Clayton
Homes
Waycross, Georgia
FSEC personnel conducted a plant visit of the Clayton
Homes factory in Waycross, Georgia in June 2002. A singlewide
home was tested and observations recorded of home and
duct construction techniques. Findings and remedies for
leaky ducts found during the visit were reported to factory
representatives in a follow-up trip report (see Appendix
A).
|