Building
America Industrialized Housing Partnership
TRIP
REPORT
Destiny Industries / Oakwood Homes
Moultrie, GA Plant Inspection
DATE
April
2&3, 2002
ATTENDEES
David
Beal, - FSEC / BAIHP
Warren
McDonald, Robert Maier - LaSalle Air Systems
Randall
Mace - Oakwood Homes Corporate Engineering Coordinator
Various
staff of Oakwood Homes of Moultrie, GA.
TRIP REPORT DISTRIBUTION LIST
George
James, Keith Bennett - U.S. DOE
D.
Beal, N. Moyer, D. Chasar, J. McIlvaine, S. Chandra -
FSEC
Mike
Lubliner - Washington State University, Energy Office
Jerry
Brooks, General Manager - Destiny Industries / Oakwood
Homes, P.O. 2947, Moultrie, GA. 31776-2947
Mark
Ezzo, Vice-president of Product Engineering, Randall
Mace, Engineering Coordinator - Oakwood Homes Corporation,
P.O. Box 27081, Greensboro, N.C. 27425-7081
Phillip
Hathcock, Regional Vice-president of Manufacturing -
HBOS Manufacturing, 590 Palmer Rd, Rockwell N.C. 28138
Warren
McDonald, Production Manager - LaSalle Air Systems, 5030
Great Oak Dr, Bldg #3, Lakeland, FL. 33815-3122
PURPOSE
Oakwood
homes is a new member of the Building America Industrialized
Housing Partnership (BAIHP). This was the first visit
to inspect the factory and review the duct assemblies
of the Destiny Industries / Oakwood Homes Moultrie, GA
plant. The Moultrie facility manufactures single and
double-wide housing with sheet metal ductwork in floor
systems. A small percentage of their houses use overhead
systems made with fiberglass ductboard and flex-duct.
Leakage
from duct systems is recognized nationally as a major
cause of energy waste, poor indoor air quality, and poor
durability in site-built and manufactured housing. Supply
duct leakage and inadequate return air pathways can cause
significant negative pressures withing the building.
Negative pressures pull in outside air (which if located
in the hot, humid South) that can result in severe moisture
damage to building envelope assemblies.
Oakwood
Homes has recently instituted a corporate policy to address
their duct systems and make them leak free, both to aid
energy efficiency and to reduce moisture related service
calls in the hot, humid coastal regions. Oakwood requested
assistance from BAIHP partner LaSalle Air Systems, who
in turn recommended that Oakwood join the BAIHP team.
This visit served to familiarize Oakwood with the BAIHP
team, and to allow BAIHP team members LaSalle Air Systems
and the Florida Solar Energy Center gauge how they can
best help Oakwood. Assistance through BAIHP’s partner
Washington State University is available for Oakwood
plants in the Pacific Northwest.
DESCRIPTION
Destiny
Industries / Oakwood Homes Moultrie, GA plant manufactures
single and double-wide housing. The plant is capable
of producing approximately 12 floors a day, but is currently
running under full capacity and producing 5 to 7 floors
a day. The majority of home produced have a sheet metal
floor duct, with a small percentage (less than one home
per day) built with an over head duct system. The floor
duct is an extruded metal duct measuring 12" by 5". Most
register boots are installed inline, with a few offset
registered installed with a side take-off collar and
a short run of flex-duct.
The
floors are built right side up, with the duct installed
over the insulation, then the floor trusses are installed
and the duct is fastened to the floor trusses with straps.
The floor is then decked, and holes are cut in the floor
for the register boot installations. A hole is cut into
the duct for the boot, and the boot is installed with
tabs and tape.
A
small percentage of their houses use overhead systems
made with fiberglass ductboard and flex-duct. A brief
time was spent observing the tools and techniques used
to manufacture overhead systems. The factory had the
necessary tools (hole cutter and strap tightening tool)
to build an adequate overhead system, and appeared to
be knowledgeable as to their use. The visiting team decided
to wait to try and introduce mastic to this system until
the factory had it on hand and was familiar with it’s
use.
OBSERVATIONS
It
was immediately apparent that there was great opportunity
for improvement in the floor system. All cutting in the
duct was being done free hand, no templates or hole cutters
being employed. The holes made for the floor registers
were cut on three sides, with the resulting flap folded
back and the register boot installed, tabbed over where
there was contact, and taped. The hole for the plenum
was made by cutting a large “X” in the duct,
folding back the flaps, then installing the plenum. Both
of these methods resulted in sloppy holes that didn’t
fit the fitting cleanly, and large amounts of tape being
used to seal gaps (when the gaps were discovered).
Exacerbating
the problem was a fairly consistent mis-alignment of
the duct. When the floor duct was installed in the floor
and strapped down, it was rarely exactly where it needed
to be, often shifted to one side or the other by several
inches. This mis-alignment, combined with the use of
a duct that is 12" wide, registers that are 10" wide,
a plenum that is 11" wide, and cross-over collars that
are 12", causes there to be large gaps where the duct
and the fittings do not meet.
Further
problems showed up due to the critical sizing of the
various components of the duct system. Even when the
duct was aligned correctly, there was installation problems
due to the corner of the duct trunk not being completely
square. When the fittings met the duct there was a gap
along the sides of the duct, as the duct didn’t
meet the fitting squarely. This was most apparent when
the 11" wide plenum was installed into the 12" wide duct.
The fittings used to do take-off ducts were 5" collars
installed into a 5" high duct. This resulted in a hole
cut into the duct that was oval, and the collar not able
to be tabbed over for the full circumference of the fitting.
The 12" cross-over collar was fit into a hole that was
cut free hand, again resulting in an oval shaped cut
that didn’t allow for full tabbing of the fitting.
Additional
opportunities were found where the end caps were installed.
The current method uses screws and tape to make the seal
on the end caps.
At
this point, due to factory floor construction scheduling,
it was convenient for the BAIHP team to try several different
duct construction methods. Partner LaSalle Air Systems
had brought along two of their register boots, a tab-over
type and a screw-down type. One home was built, with
one half of the home using screw-down boot, and the other
half using LaSalle’s tab-down boots. The trail
installation also included the use of mastic on the duct
systems.
TESTING
After
observing several floors in the factory and building
the trail duct systems, testing of the duct systems was
undertaken. Duct system
testing uses a calibrated fan (duct blaster) to depressurize
the duct system to a specific pressure, in this case
25 pascals (pa). The amount of air in cubic feet per
minute (CFM) needed to achieve this pressure is determined,
yielding a CFM25total flow number (cubic feet
per minute at 25 pa). For a duct system to be
considered to be “substantially leak free” by
BAIHP, the CFM25total must be a number that
is less than 5% of the air handler fan flow. Assuming
400 cfm per ton fan flow or 1200 cfm fan flow for a 3
ton unit (typical for a 1500 ft2 building),
and using the desired criteria of 5% of fan flow, the
target CFM25total would be less than or equal
to: (3 ton * 400 cfm/ton) * 0.05 = 60 CFM25total.
As testing in the factory was done on half houses (double
wide tested one floor at a time) the desired CFM25total number
would be 30 or less.
The
first floors to be tested was the home built just before
the test home was constructed. This was a 14' X 56' (per
side) double wide. The CFM25total on the air
handler unit (AHU) side was 80, the non-AHU side had
results of 48. This was a 1568 ft2 home. Assuming a 3
ton A/C unit, with a fan flow of 1200 CFM, this represents
a CFM25total (80 + 48 = 128) of more than
10% of the fan flow.
The
next house to be tested was the trial floor. This was
a 1456 ft2 double wide. The AHU side employed the screw-down
boots and had a CFM25total 47. The non-AHU
side used tab-over boots and had a CFM25total of
25. Again, assuming a 3 ton A/C unit, with a fan flow
of 1200 CFM, this represents a CFM25total (47
+ 25 = 72) of 4% of the fan flow. This was an encouraging
result, but the team felt that they could do better.
Examination of the screw down boot revealed that due
to a layer of insulation installed between the floor
trusses and the duct the duct was approximately 1" lower
than the LaSalle screw-down boot was designed for. This
made the installation difficult, and also allowed there
to be leaks where the boot did not sit firmly on the
duct.
The
results of testing the trail floors, compared to the
testing of a standard production floor did not convince
the production staff of the factory of the need to stop
using foil tape and start using mastic to assemble their
duct system. The staff felt that if the tape was properly
installed it would provide adequate results. The BAIHP
team members believe that foil tape will fail unless
applied according to manufacture’s instructions.
These instructions are typically ignored, as there is
a requirement for surfaces to be clean and free from
oil. The duct material is coated with oil when manufactured,
and the duct manufacturing machine gets even more oil
on the duct material. It is unlikely that there would
be adequate oil cleaning in the factory, and cleaning
solutions might impact employee health by subjecting
them to high levels of volatile organic chemicals. The
BAIHP team felt that it was critical to convince the
factory personnel of the merits of mastic compared to
tape. To this end, several older homes were found on
the factory’s back lot and inspected and tested.
The
first older house inspected was an 18 month old double
wide that had remained on the factory’s lot since
construction. The duct system showed very poor workmanship,
with large gaps in the duct system never taped, and to
a lesser extent, tape failure. The CFM25total of
the AHU side of this home was 200. The staff still felt
that proper tape installation would be sufficient, and
proceeded to re-tape the home. After this effort, the
home was retested and yielded a CFM25total of
70. This relatively poor result started to convince the
staff that tape was not the answer. The inspection continued
with a 18 month old single wide that also had remained
on the factory lot since construction. The same problems
were evident, poor workmanship and tape failure starting.
Both of these houses had never been occupied, and no
heating or cooling had occurred to help the tape fail.
After a brief search, a repossessed unit was found to
inspect. This home had been occupied for approximately
one year, and then repossessed by the factory. Here the
inspection reveled sever problems. There was significant
mold growing along the marriage line ceiling. The duct
system’s tape was failing at an alarming rate,
as well as poor workmanship in the duct system. Mold
growth along marriage lines has been observed by BAIHP
team members in the field, and is most often the result
of several causes, all related to duct leakage. The mold
growth, combined with the obvious evidence of tape failure,
convinced the factory staff that foil tape most likely
will fail when improperly applied to a metal duct system.
The
BAIHP team and factory staff returned to the floor department
and assembled a final floor duct system. The desire was
to take all of the techniques developed during the trip
and build a very tight duct system. the factory staff
felt that the screw down register boots offered a better
sealing option than the tab-over boots. The system was
fabricated using the screw-down register boots. The plenum
was installed correctly, and sealed with several tubes
of mastic (extra mastic was needed due to the non-900 corner
of the trunk duct, resulting in the side of the plenum
not fully contacting the duct. The resulting gap was
sealed with mastic. The cross-over drop-out was also
installed and sealed with mastic. After construction
the half home’s duct system was tested, yielding
a CFM25total of 50. The team was not satisfied
with this number, so further inspection and testing was
carried out. First, the AHU was removed and the ducts
retested. This resulted in a CFM25total of
32, or showing that the AHU represented a CFM25total approximately
20. This result was still not as tight as desired, so
a through visual inspection of the duct system was undertaken.
This inspection reveled that the cross-over collar was
not well sealed, and there were several gaps under the
screw-down boots (again, due to the duct’s non-900 corner
). After resealing all of the visible duct leakage the
home was retested and had a CFM25total of
20. Although this result was not a good as hoped for,
it represents a “substantially leak free” duct
system.
CONCLUSIONS AND RECOMMENDATIONS
All
of the observed problems in the duct system stem from
two problems, poor workmanship and materials, and the
use of a duct system that is 12" wide. The workmanship
problems are easily rectified with worker and QC training,
combined with a more rigorous inspection protocol. Specific
items to be addressed are as follows:
• Change
over to a 14" wide duct. The 12" duct requires very careful
alignment, and even then is not without problems when
attempting to install an 11" plenum, 12" cross-over collars,
and 10" register boots.
• Install
all plenums, register boots and collars with mastic,
DO NOT use tape.
• Use
top take-off fittings for doing offset registers. The
current 5" side-take-off collar installed into a 5" high
duct is leaky, and time consuming. A top-take-off collar
goes into the top of the duct, screws down, and is easily
sealed with mastic. LaSalle Air Systems can provide this
fitting.
• To
correctly employ a screw-down register boot it must be
redesigned by LaSalle Air Systems to fit in Oakwood’s
floors, as it currently is designed for ducts without
a layer of insulation on top. There was some indication
that LaSalle’s tab-over register boot could be
taller also.
After
the obvious problems are solved by the production crew
at Oakwood, further testing needs to be done to insure
that the duct tightness criteria are being met by the
new practices. Also worthy of investigation is the sizing
of return air pathways from bedrooms. Typical HUD-code
homes have inadequate return air pathway from bedrooms,
causing sustained negative pressures in the house when
bedroom doors are closed.
For
questions or comments on this trip report, please contact
the author, David Beal at 321-632-1433 or via email at
david@fsec.ucf.edu.