Click here for PDF Version
Abstract
Four occupied homes near Dallas, Texas were monitored to compare
cooling energy use. Two homes were built with typical wood
frame construction, the other two with insulated concrete
form (ICF) construction. Remote data loggers collected hourly
readings of indoor and outdoor temperature, relative humidity,
furnace runtime fraction, total building electrical energy
and HVAC energy use. Data was recorded from January through
August 2000.
Analysis of the measured data shows that insulated concrete
form (ICF) construction can reduce seasonal cooling energy
use 17 - 19% over frame construction in two-story homes in
the North Texas climate. This result includes adjustments
to compensate for differences in miscellaneous energy use,
(e.g. lights & appliances), and duct leakage. While each
home pair had the same floor plan, elevations and orientation
there were some differences that were not accounted for in
the measured results. These included occupant impacts, exterior
wall color (absorptance) and the absence of an attic radiant
barrier in one ICF home.
In
addition to analyzing the measured data, two sets of DOE2
simulations were performed. An initial comparison of ICF and
frame homes modeled in their as-built condition was followed
by a comparison of homes modeled with identical features except
for wall construction. Both analyses showed a 13% annual cooling
energy savings for ICF over frame construction. This result
is comparable to a similar simulation study (Gajda 2001) of
a two-story home in the Dallas climate, which saved 15% annually
on both heating and cooling.
Introduction
Four
Centex homes near Dallas, Texas were monitored by the Florida
Solar Energy Center as part of the Building America Industrialized
Housing Partnership (BAIHP). Centex Homes and the Portland
Cement Association are two BAIHP partners that were involved
with the study. Two home models (Figure 1) were constructed
twice; one with typical wood frame construction and the other
using insulated concrete forms (ICF).
Each home was tested to determine building airtightness and
the amount of duct leakage. Table 1 shows test results and
other relevant building details. Figure 2 illustrates wall
construction for each home type.
Figure 1. Two Home Models
According
to conventional wisdom and manufacturer’s claims, the
ICF homes should benefit from a higher and more consistent
level of thermal insulation as well as greater airtightness
wherever insulated concrete forms replace wood framing. The
envelope airtightness measurements in Table 1 (CFM50 and ACH50)
however, show that in one case the ICF home was tighter than
the frame home while in the other the trend was reversed.
This may be attributed to the fact that only the walls of
the ICF homes were constructed differently from the frame
structures, while the slab-on-grade foundation and wood-framed
roof designs were similar. Construction details at the attic
and at the junction of the first and second floors are critical
to the airtightness of these homes, as is the amount of duct
leakage.
Table 1. Building Construction &
Airtightness Details
Construction |
ICF
|
Frame |
ICF |
Frame |
Model |
E2051 |
E2051 |
E50 |
E50 |
Floor Area (ft2) |
3,767 |
3,767 |
2,861 |
2,861 |
Heat Pumps 1st/2nd
fl. |
5 ton /4 ton |
5 ton / 4 ton |
4 ton / 2.5 ton |
4 ton / 2.5 ton |
Glass/Floor Area |
18% |
18% |
13.5% |
13.5% |
Attic Radiant Barrier |
No |
Yes |
Yes |
Yes |
Exterior Brick Color |
Red w/Black Tint |
Red |
Red w/Pink Tint |
Red |
CFM50 |
2,701 |
3,105 |
2,632 |
2,426 |
ACH50 |
4.3 |
5.0 |
5.6 |
5.1 |
CFM25 total |
620 |
742 |
602 |
674 |
CFM25out |
268 |
407 |
296 |
385 |
Occupancy
|
6 |
4? |
4 |
4 |
Notes:
- All homes are 2-story with the front facing north
- All windows are double pane, clear glass, aluminum frame,
U=0.81.
- All attics have R-30 blown insulation.
- SEER 12 Heat pumps were designed to run until the outside
temperature reached 47°F after which natural gas backup
heat came on. (no electric strip heat) |
Data
Collection And Analysis
Remote
data loggers collected hourly readings of indoor and outdoor
temperature, relative humidity, furnace runtime fraction,
total building electrical energy and HVAC energy use. Data
were recorded from January through August 2000.
Isolating cooling energy use from the measured HVAC energy
data provided the most useful and straightforward comparison.
Analysis of heating energy use was complicated by the use
of electric heat pump units backed up by a gas furnace. Consequently,
heating control strategies were not consistent between homes.
To
assess the cooling energy difference between the frame and
ICF homes the average daily indoor to outdoor temperature
difference (delta T) was plotted against the total daily cooling
energy use. All hours between Jan 1 and Aug 23 (the last full
day of data) were used in this analysis but only the hours
where the ambient temperature was above 65°F are included.
This allowed the isolation of those hours in which cooling
is taking place regardless of the time of year. In some cases
only a few cooling hours from a given day were included, while
in others all 24 hours were used. The average daily indoor
temperatures (IDT) were derived from the same hours when ambient
temperature was
Figure 2. Frame and ICF Wall Construction Details
above
65ºF. Indoor temperatures were recorded hourly at the
return plenum on each floor
and averaged together.
Normalized
Cooling Energy
In comparing both pairs of homes it was found that the ICF
buildings consistently used less miscellaneous energy (lights,
appliances, etc.) than the frame structures. While no attempt
was made to monitor or survey these energy end uses, they
could be isolated by subtracting HVAC energy from total building
energy use. Reducing the energy data of both frame homes provided
a more conservative comparison since much of the miscellaneous
energy use would be added to the home in the form of heat
that the air conditioner must then remove. Water heating energy
was not a factor here because it was provided by natural gas,
however the units were located in the conditioned space.
To normalize the comparison, the daily cooling energy in each
frame home was reduced by subtracting the difference in miscellaneous
energy between each ICF and frame home pair while factoring
in the COP of the air conditioning equipment (Equation 1).
Figures 3 and 4 show the collected data after this adjustment
and the resulting trend lines.
Equation 1. Normalized Frame Cooling
Energy
(Cooling kWh)frame = (Cooling kWh)frame
– [(Misc.kWhframe – Misc.kWhICF)
/ COPAC]
Figure 3. Normalized Energy Cooling Comparisons for Model
E50.
Figure 4. Normalized Energy Cooling Comparisons for Model
E2051.
Duct
Leakage Impact
Analysis of the measured data was also complicated by the
fact that, while the duct systems in each model were the same,
both ICF homes had tighter ducts than their frame counterparts
(see CFM25 in Table 1). Since this random variation would
favor the ICF homes, DOE2 simulations were performed to estimate
the impact. Using the E50 model home and TMY2 weather data
for Fort Worth, Texas; DOE2 simulations were performed with
a 76ºF setpoint. Results showed that increasing the duct
leakage in proportion to that found in Table 1 (CFM25out)
increased cooling energy use by about 4%. This then was added
to the ICF energy use in the final comparison below.
Measured
Seasonal Cooling Savings
Including adjustments for differences in miscellaneous energy
use and duct leakage, the measured data shows that, in both
models, the ICF home used less cooling energy than the home
built with conventional frame construction. Measured savings
of ICF construction over frame during the Dallas cooling season
are shown in Table 2. These values were derived from the linear
fit equations of Figures 3 and 4 as detailed in the Table
2 notes. Note that the final savings values in Table 2 were
decreased 4% to account for duct leakage differences as described
above.
Table 2. Measured Seasonal Cooling
Savings – ICF over Frame Construction
|
Type |
Slope |
Intercept |
Energy(kWh) |
Cost |
Savings |
Adj. Savings |
E2051(3,767 ft2) |
Frame |
1.486 |
19.71 |
4,448 |
$356 |
22.9% |
18.9% |
ICF |
1.351 |
13.90 |
3,429 |
$274 |
|
|
E50(2,861 ft2) |
Frame |
0.999 |
12.41 |
2,862 |
$229 |
20.8% |
16.8% |
ICF |
0.932 |
8.95 |
2,268 |
$181 |
|
|
Notes:
- Energy = [slope x (82.3 – 76) + intercept]
x 153
Where: |
82.3 = average summer ambient
temperature (ºF) |
|
76.0 = average cooling setpoint (ºF) |
and |
153 = Dallas cooling season (May 1 through
September 30) |
- Frame home energy was reduced in Figures 3 &
4 to account for differences in miscellaneous energy
use
- Final savings values were reduced 4% to account
for duct leakage differences
- Utility rate of $0.08/kWh used to obtain cost savings
|
Occupant
Impacts
Occupant activity and homeowner habits can have a major impact
on residential energy use. Each of the four homes had at least
4 occupants (E2051 ICF home had 6 occupants). No other measure
of occupancy or occupant activity was recorded during the
study period.Two sources of occupant impacts were factored
out of the measured data. One by describing HVAC energy use
in terms of the difference in temperature across the building
envelope, which helps account for thermostat settings, and
the other by accounting for the difference in miscellaneous
energy use between each home pair. Some examples of occupant
activity that could not be accounted for include:
- The
level of interior shade usage
- The
amount of outdoor air allowed to enter the home
- Moisture
released inside the home by cooking and cleaning activities
-
Long-term interior door closure in rooms where insufficient
return air pathways exist
Wall
Solar Absorptance and Radiant Barriers
Despite
efforts to build each pair of homes with identical construction
except for the wall assemblies, two oversights existed –
exterior brick color differed between each home pair and an
attic radiant barrier was absent in one of the ICF homes.
The solar absorptance level of exterior walls can have a measurable
effect on the space cooling load. This effect is even more
pronounced in two-story homes where the wall surface area
is much greater than with single story construction and where
roof overhangs are less beneficial. Brick colors for the four
homes are described in Table 1 and the two pictures visually
show the difference. In the Model E2051 comparison, the frame
home had the lighter (more favorable) brick color, whereas
the ICF home had the lighter color in the E50 model comparison.
Three of the homes had roof decking with radiant barrier laminated
to the underside to reduce radiant heat transmission to the
second floor space. The model E2051 ICF home however did not
have this benefit and received a greater cooling load as a
result.
DOE2
Simulation Analysis
One
set of matched-pair homes (Model E50, Frame & ICF) was
analyzed using DOE2 simulation software to corroborate the
measured data results. The software called EnergyGauge USA®
(Parker et al. 1999), provides an input interface for performing
hourly computations with the DOE2.1E simulation engine. Annual
simulations were performed using the TMY2 weather data for
Fort Worth, Texas.
A rough comparison of the measured data with the TMY2 data
set (Table 3) shows that the weather was slightly warmer in
2000 than the typical meteorological year. Cooling degree-days,
which may approximate energy use, were 13% higher during the
data collection period from January through August. The average
ambient temperature from May through August was also higher
in the collected data (82.3 ºF) versus the TMY2 data
for the same period (79.8 ºF).
Table 3. Comparison of Measured
vs. TMY2 Weather Data
|
Measured Data (2000) |
Ft. Worth TMY2 Data |
Cooling Degree-Days (Jan –
Aug) |
2,225 |
1,939 |
Average Seasonal Summer Temperature
(May – Aug) |
82.3 ºF |
79.8 ºF |
The
computer simulations were used for two purposes: (1) Authenticate
the measured savings by comparing it with DOE2 models of frame
and ICF homes in their as-built condition, and (2) Provide
estimated savings of ICF over frame with identical construction
except for the makeup of exterior walls. The variation in
brick cladding color on each home pair was expected to have
a significant impact on the cooling energy use (Parker et
al. 2000). Ideally, solar absorptance would have been measured
for the actual bricks used in each home, instead estimates
taken from Table 4 were used in the simulations (BIA 1988).
Table 4. Absorptivity of Brick
Brick Color |
Absorptance |
Flashed (Blue) |
0.86 – 0.92 |
Red |
0.65 – 0.80 |
Yellow or Buff |
0.50 – 0.70 |
White or Light Cream |
0.30 – 0.50 |
Source: Brick Industry
Association. Technical Notes 43D |
Authentication
of Measured Savings
DOE2
simulations of the model E50 frame and ICF homes were performed
with identical inputs except for brick color, thermostat setting,
building leakage and duct leakage. Input values and final
results are shown in Table 5. The simulations showed a savings
of only 13% as compared with the 17 to 19% found in the measured
data after adjusting for duct leakage differences in both
data sets. Note that the 17 to 19% savings determined from
the measured data was a seasonal cooling estimate for the
period from May through September, while the 13% savings found
in the simulation results is taken from cooling energy use
for the entire year. Although confidence in the measured results
is reduced due to the small sample size, the DOE2 simulations
support the measured analysis.
Table 5. DOE2 Inputs and Results – As-Built
Simulations
Construction |
Absorptance |
Cooling Setpt |
ACH50 |
Qn |
Cooling Energy |
Savings |
Adj.Savings |
ICF |
0.55 |
75ºF |
5.6 |
0.105 |
6,200 kWh |
15.90% |
12.90% |
Frame |
0.88 |
76ºF (prog) |
5.1 |
0.135 |
7,375 kWh |
|
|
Annual
cooling load distributions were also derived from the as-built
simulation set (AEC 1992). The pie charts in Figure 5 represent
the cooling load components in each home as constructed and
tested including the differences found (brick color, thermostat
setting, building and duct leakage). Although internal gains
differed in the monitored homes, they are held constant here.
The charts show the strong impact of changing the wall construction
and absorptance of the brick cladding (solar absorptance of
0.55 for ICF home and 0.88 for frame home).
Figure 5. E50 Cooling Loads - As-built Comparison
Ideal
Comparison of ICF and Frame Construction
Another
set of DOE2 simulations were performed with the Model E50
home to determine the value of ICF over frame when the only
difference between the homes existed in the wall construction.
In this case all other parameters were held constant including:
wall absorptance, thermostat setting, building airtightness
and duct leakage. As shown in Table 6, the 2-story ICF home
saves about 13% in annual cooling energy over a similar frame
home. In another 2-story home simulation study (Gajda, 2001)
with many similar characteristics to the E50, ICF construction
saved 15% over frame in the Dallas climate. Gajda’s
value included both heating and cooling energy use however
and brick cladding was not present in either wall design.
Table 6. DOE2 Inputs and Results
– Ideal Comparison
Construction |
Absorptance |
Cooling Setpt |
ACH50 |
Qn |
Cooling Energy |
Savings |
ICF (R-20) |
0.7 |
78ºF |
5 |
0.105 |
5,206 kWh |
12.90% |
Frame (R-13) |
0.7 |
78ºF |
5 |
0.105 |
5,980 kWh |
|
Notes: Differences in DOE2 input deck
were limited to wall construction properties as detailed
in Figure 2
Qn represents duct leakage as a percent of floor area
(Qn=CFM25out/floor area) |
Figure 6 illustrates the annual cooling load
distributions (AEC 1992) when comparing frame and ICF homes
that are identical except for their wall construction. These
results give an estimate of the true impact of only changing
the wall construction while holding all other parameters
constant.
Figure 6. E50 Cooling Loads – Ideal Comparison
Conclusions
Measured
data collected in two nearly matched-pair homes shows that
insulated concrete form (ICF) construction can save 17 to
19% over the cooling season with two-story homes in the North
Texas climate. Adjustments to the measured data were made
to compensate for differences in miscellaneous energy use
(e.g. lights & appliances), and duct leakage. Differences
not quantified here included occupant impacts, exterior wall
color (or absorptance) and the absence of an attic radiant
barrier in one of the four homes.
In addition to analyzing the measured data, two sets of DOE2
simulations were performed. An initial comparison of ICF and
frame homes modeled in their as-built condition was followed
by a comparison of homes modeled with identical features except
for wall construction. Both analyses showed a 13% annual cooling
energy savings for ICF over frame construction. This result
is comparable to a similar simulation study (Gajda 2001) of
a two-story home in the Dallas climate, which saved 15% annually
on both heating and cooling.
Relative cooling savings of ICF versus frame construction
would be smaller in single story homes due to smaller wall
areas. Two-story construction makes up 33% of US housing (DOE/EIA
1995), with single story being much more common. Cooling energy
savings on single story construction could amount to only
half of that found in this study.
Further research is needed to more precisely quantify the
energy benefits of insulated concrete form homes. Such research
should compare homes that are identical in every aspect except
wall construction and ideally should be monitored without
occupancy or with simulated occupancy. Results of such carefully
controlled experiments and subsequent analysis by validated
hourly simulation software can provide a more accurate estimate
of the benefits of ICF construction. Any analysis of occupied
homes would require monitoring of a statistically valid (large)
sample of ICF and conventional residences.
Acknowledgments
This research was sponsored, in large part, by the U.S. Department
of Energy, Office of Building Technology, State and Community
Programs under cooperative agreement no. DE-FC36-99GO10478
administered by the U.S. DOE Golden field office. This support
does not constitute an endorsement by DOE of the views expressed
in this report.
The authors appreciate the encouragement and support from
George James, program manager in Washington DC and Keith Bennett,
project officer in Golden CO. Special thanks also go to Randy
Luther of Centex Homes who made this study possible. His support
and encouragement are greatly appreciated.
References
Architectural Energy Corporation (AEC). 1992. Engineering
Methods for Estimation Inputs of Demand Side Management Programs.
Palo Alto, CA. EPRI TR-100984, Volume1 pg. 2-28 through 2-31.
Electric Power Research Institute.
Brick Industry Association (BIA). 1988. Technical Notes 43D
- Brick Passive Solar Heating Systems Part 4 - Material Properties.
Reston, VA.
DOE/EIA. June 1995. Housing Characteristics, DOE/EIA-0314,
Table 3-1.Washington D.C. Energy Information Administration.
Gajda, John. 2001. Energy Use of Single-Family Houses with
Various Exterior Walls. CD026. Skokie, IL. Portland Cement
Association.
Parker, D., P. Broman, J. Grant, L. Gu, M. Anello, R. Vieira
and H. Henderson. 1999. EnergyGauge USA: A Residential Building
Energy Design Tool. Proceedings of Building Simulation '99,
Kyoto, Japan. International Building Performance Simulation
Association, Texas A&M University, College Station, TX. |