II.
BAIHP Technical Assistance (N)
- Nez
Perce Fish Facility
Cle Elum, Washington
Three SGC homes were built at the Nez Perce tribal fish
facility in Cle Elum, WA. One of these homes is equipped
with Energy Star appliances and lighting; all three homes
are heated with Insider heat pumps. Monitoring equipment
was installed in Year 2. In Year 3, preliminary blower
door testing indicated a high leakage rate. During Year
4, tests found significant duct leakage due to failure
of butyl tape at risers on 2 year old home. (See also Section
III Research Zero Energy Manufactured Home.)
- New
Generation Homes
Ft.
Myers, FL
|
Figure 31 New Generation
Home |
Ken Kingon of New Generation Homes became
a BA partner at the end of the 5 th budget period.
Of particular interest is the performance of the high
efficiency 5 ton 15 SEER AC system and the use of outside
air ventilation (measured air flow = 32 cfm) to the
air handler. A house was tested and instrumented in
February 2005 by FSEC researchers, showing that duct
leakage and air tightness are consistent with new home
construction, there are opportunities for improvement.
The HERS score is 87.9.
- Northwest
Energy Efficient Manufactured Housing Program (NEEM)
Idaho
Oregon
Washington (State)
The Washington State University Energy Program (WSU),
together with partners Oregon Office of Energy and Idaho
Department of Water Resources, Energy Division, continue
to provide technical and research support to the Northwest
Energy Efficient Manufactured Housing Program (NEEM program
in the Pacific Northwest. The NEEM program involves 20
plants in three states, hundreds of retailers and thousands
of homebuyers.
The NEEM program includes the brands Super Good Cents
and ENERGY STAR, and includes homes heated by electricity
and Natural Gas/propane. Prior to 2003, the NEEM program
also included the Natural Choice brand, which was exclusive
to homes heated with Natural Gas or propane. In 2003,
the Natural Choice brand was phased out; now, all gas
heated homes are branded ENERGY STAR. In 2004, a new
path for ENERGY STAR was developed for Super Good Cents
homes with electric furnaces. Homes will be built to
this path beginning in 2005.
In the fall of 2004, NEEM staff began to provide technical
assistance to Champion Homes on a 700 unit private military
modular housing development at Ft. Lewis. In-plant verification,
certification and on-site verification of these homes
began in spring of 2005 and will continue as a major
BAIHP effort.
In the fall of 2004, technical assistance by NEEM staff
to the Energy Trust of Oregon resulted in the development
of a million dollar utility incentive program that promotes
the production of a more NEEM homes built to higher benchmarking
levels consistent with BAIHP goals. A technical analysis
of the ETO program has been provided to FSEC.
Throughout the BAIHP effort, WSU staff provided technical
assistance and guidance to the NAHB Research Center Energy
Value Housing Awards, judging submittals, providing de-briefing
to builders, and participating on workshops. NEEM builders
Fleetwood, Champion, Valley and Marlette have received
EVHAs for factory built housing.
Aligning with New Building America Goal
In
the summer of 2004, BAIHP staff performed a benchmarking
evaluation to assess the improvement of NEEM homes over
the entire BAIHP project period (note that this evaluation
was included in the Year 5 (April 2003 – March
2004) annual report). The benchmarking was based on
a home defined by NREL (built to IECC requirements).
The savings over the benchmark home were estimated
using version 2.2 of Energy Gauge USA. Evaluations
were performed for a typical 1600 ft 2 double wide
home with 12% glazing to floor area (the NEEM fleet
average) in three Pacific Northwest climate zones:
Portland, OR; Spokane, WA; and Missoula MT.
The homes were benchmarked assuming a continuously
operating whole house ventilation system, resulting in
a significant thermal energy penalty. Additional benchmarking
was also conducted using the 164 kWh/year ventilation
assumption in the NREL benchmark, in an effort not to
penalize the homes for improved IAQ associated with HUD
whole house ventilation system requirements and ASHRAE
62.2.
In 2004-2005, improvements were made to NEEM HVAC systems
and duct specifications as a result of BAIHP research
(see Refinement of NEEM Specifications, below.) Additional
benchmarking is presented that reflects these improvements.
The results of the benchmarking vary considerably by
HVAC type, water heat and climate, as noted in Table
19 below. Some key observations:
- In all climate zones, electric homes result in negative
savings if the ventilation penalty is assumed.
This is largely the result of the assumption that
the benchmark home has a heat pump that performs without
installation problems; an assumption that will be
evaluated by BAIHP research.
- Gas heated NEEM homes came closest to meeting the
overall BAIHP goal of 40% over the NREL
benchmark, but only met the goal if gas heat is paired
with electric water heat, in cold climates with no
ventilation system penalty.
- Eliminating the ventilation system penalty has a
higher impact on benchmarking results (9
to 23 percentage points) than improved duct leakage tightness
(3 to 11 percentage points).
- It should be noted that
Benchmarking these NEEM homes against the HUD-FMCSS requirements
(Uo=.079) for manufactured homes rather than the
IECC (Uo=0.06) would yield considerably higher savings
than current benchmark assumptions.
Table
19 Benchmarking Savings Results |
Duct Leakage |
Pre-2004* |
2004** |
Pre-2004* |
2004** |
Ventilation System Penalty |
Yes |
Yes |
No |
No |
Portland |
Electric Furnace |
-31 |
-20 |
-8 |
0 |
Heat Pump |
11 |
14 |
20 |
22 |
Gas Heat/Elec DHW |
16 |
22 |
32 |
37 |
Gas Heat/Gas DHW |
15 |
20 |
30 |
34 |
Spokane |
Electric Furnace |
-18 |
-9 |
2 |
10 |
Heat Pump |
17 |
21 |
27 |
30 |
Gas Heat/Elec DHW |
22 |
27 |
36 |
41 |
Gas Heat/Gas DHW |
21 |
26 |
35 |
39 |
Missoula |
Electric Furnace |
-12 |
-3 |
8 |
15 |
Heat Pump |
17 |
22 |
28 |
32 |
Gas Heat/Elec DHW |
21 |
26 |
35 |
40 |
Gas Heat/Gas DHW |
20 |
25 |
34 |
38 |
*
Pre-2004 – Duct
leakage of -132 cfm@25PA
** 2004 – Duct leakage
of -60 cfm@25PA
|
Figure 32 shows, by program year,
the number of homes produced with technical assistance from
BAIHP, as well as the number of homes submitted for ENERGY
STAR designation by BAIHP staff and the breakdown of homes
by benchmarking score. Please note the following:
- The benchmarking includes the assumption, based
on the NEEM 5 th Budget Period random that
showed 24% of all homes included after-market heat
pumps.
- No benchmarking was performed for Years 1 and 2,
due to a lack of accurate regional data.
- In 2003 and 2004, the appearance of homes that achieved
a 30+% benchmark is the result of the improvements
made to the NEEM HVAC specifications.
- Figure 32 averages benchmarks for Spokane and Missoula
for homes in cold climates and uses the
Portland benchmark for marine climates. Figure 32 also
assumes an average value between ventilation penalty
and no ventilation penalty.
The continued success of the program is due to several
factors. BAIHP and NEEM staff worked to increase awareness
within the manufactured housing industry of the marketing
value of energy efficiency, increase participation by
utilities in incentive programs, and promote the co-branding
of NEEM with ENERGY STAR.
Figure 32 Homes Produced
with BAIHP Technical Assistance
The
increase in ENERGY STAR designations is due to refinement
of the SGC duct sealing specifications, resolving a discrepancy
between the SGC specifications with ENERGY STAR’s duct
sealing protocols (while this question was being resolved
September of 1999 through early 2001, BAIHP staff did not
submit homes to DOE for ENERGY STAR designation). In 2003,
remaining discrepancies with manufacturers in Idaho were
further resolved, allowing BAIHP staff to accurately report
all qualifying homes.
Refinement of SGC specifications
BAIHP staff continually work to refine the existing SGC
specifications, a result in large part to innovative building
technologies researched in BAIHP.
In 2003, BAIHP staff worked with NEEM staff and manufacturers
to develop revisions to NEEM specifications, including allowing
only mastic for duct sealing, requiring metal flex duct for
whole house ventilation fans, and changing the air infiltration
specification from 7.0 ACH 50 to 5.0 ACH 50.
The revised specifications were voted on and accepted by
the manufacturers; they took effect on January 1, 2004.
In
year 2004 in Oregon, 1 in Idaho plant began testing the
ducts in all the NEEM homes they produce, which is expected
to result in even tighter duct systems. Field testing of
a sub-sample of these homes duct testing began in 2004
and continues. This field testing is also evaluating homes
that employed a “thru-rim” crossover duct system.
BAIHP staff continues to work with EPA and other regional
partners on clarifying the equivalency of SGC with ENERGY
STAR. In 2002, BAIHP staff developed a new ENERGY STAR compliance
path for climate zone 2 that does not require a heat pump.
The non-heat pump path uses a heat recovery ventilation system,
a .93 EF hot water heater and tighter ducts and envelope.
This path was not utilized due to reluctance by manufacturers
to install HRV systems. In 2004, this path was modified to
eliminate the HRV, and include options such as set-back T-stats,
ENERGY STAR dishwasher, adjusted glazing limits, improved
window U-factors, and in-plant tested duct systems.
Revised In-plant Manual
In 2003, in light of the revisions to the NEEM specifications,
BAIHP staff from the Oregon Department of Energy developed
an updated in-plant inspection manual, with new graphics,
including details on correct installation of heat recovery
ventilation. Many of the manual updates are the result of
BAIHP research and demonstration efforts, including use of
hybrid floor systems and proper duct sealing with mastic.
The manual also now includes a regionally consistent problem
home inspection protocol.
In-plant QC Training
In 2004, BAIHP staff from the Oregon Department of Energy
developed a PowerPoint presentation, based on the revised
In-plant manual. In 2004, BAIHP staff began using this presentation
to train QA staff at each plant; this effort will continue
until all NEEM plants have received this training.
In-Plant Inspections
On
a quarterly basis, BAIHP staff visits each of the manufactured
housing plants to verify compliance with SGC/E-Star specifications.
Inspections include a plant audit, ventilation system testing,
and troubleshooting construction-related problems with plant
staff and independent inspectors. Consistent issues in the
plant include wall insulation compression or voids due to
improper cutting of batts, attention to duct installation
and air sealing. Specific in-plant inspection reports conducted
in Washington in program Year 6 (March 2004 – April
2005) are provided to FSEC.
Transition to mastic
As
mentioned above, the NEEM program eliminated the use of
butyl tape for duct sealing, and required the use of mastic.
As of spring 2004, ten manufacturers have successfully
transitioned to mastic. Testing in-plant has indicated
significant improvement in duct leakage rates of homes
in these factories– an
average 36.8 cfm @ 25 PA (versus 50.1 cfm @ 25 PA pre-mastic),
a 27% improvement. This trend continued into 2005.
WSU and ODOE began working with Fleetwood engineers to
evaluate a new lower cost duct leakage testing device that
Fleetwood is considering using in all of its plants throughout
the USA. The preliminary results suggested a need utilize
10 second averaging and set a higher pressure ratio from
86% to 90% to be consistent with NEEM duct leakage targets.
This work will continue through program Year 7.
Duct Workshops
Through the spring of 2005, BAIHP staff continued to provide
workshops focused on improved duct installation and inspection
oversight, working in partnership with BAIHP partners. One
in-plant duct leakage workshop resulted in the identification
of significant duct leakage (branch disconnect) which re-enforced
the need to consider duct testing of all units at that plant. New Technology Evaluations
High
Efficiency Gas Furnaces
|
Figure
33 90% AFUE
Furnace, as installed at Kokanee Creek |
Initial
evaluations of 90% efficient gas furnaces indicates that
there is no incremental installation cost to the use
of these furnaces, as no field modifications are required.
In 2003, Nordyne and Evcon came out with furnaces with
an appropriate footprint for manufactured housing; Intertherm
also continues to offer a 90% efficient model. Discussion
with BAIHP home manufacturer partners Fuqua, Marlette,
Champion, and Fleetwood, and furnace manufacturer partners
Evcon and Nordyne, indicate the that this market is growing
quickly, especially in homes with high pitch “tilt-up” roof
systems, and multi-story homes such as at Nogi Gardens
and Kokanee Creek. The ability to use wall venting instead
of roof venting with condensing furnaces makes them more
attractive where tilt-up roofs are employed.
Through the rim crossover duct system
Three
Oregon manufacturers, Marlette, Skyline and Homebuilders
Northwest, adopted a crossover duct system that runs through
a cut out section of the rim joist, effectively placing
the entire crossover system in the heated space. A gasket
on the marriage line provides a seal between sections.
Challenges with the use of this system include the need
for very accurate measurements to insure matching of the
duct connection, and careful treatment of the gasket material
during set up, so that it doesn’t detach from the
rim.
Evaluations suggest that that further improvement to
gasket systems may be needed to ensure set-up that achieves
effective duct sealing.
La Salle Duct Riser
BAIHP
staff worked with BAIHP partner La Salle Air to design
and produce a duct riser for manufactured homes that
uses mastic instead of tape. BAIHP staff demonstrated
prototype designs of the riser to Northwest manufacturers
in Year 3. Most NEEM manufacturers adopted the new risers
or equivalent systems in year 6. . BAIHP staff worked with
Fleetwood’s national office to promote the use of
the riser in all Fleetwood plants. During 2003-2004, BAIHP
staff promoted the use of this technology at the annual
MHI conferences and energy road-mapping meetings.
Flexible Technologies:
BAIHP
partner Flexible Technologies has developed innovative
systems that improves the heat and tear resistance of the
duct inner liner, reduces the crimping of ductwork without
the use of sheet metal elbows, and an improved system to
air seal where the crossover duct penetrates the bottom
board. BAIHP staff evaluating the use of this system in
the WSU Energy House and ZEMH, and worked with Flexible
Technologies staff to promote the use of the new system
to the region’s manufacturers. Efforts to gain market
adoption of the technology remain challenging due to first
cost increases and lack of demonstrated benefits.
Figure 34 Insider Heat Pump
in ZEMH and Base Home –
Operation in HP and Strip
Heat Mode
Insider Heat Pump
Monitoring of the Insider heat pump at the WSU Energy
House was begun in 1999. Measured flow rate of the indoor
unit was good (850 CFM total, 425 CFM per ton), but BAIHP
staff identified two performance issues: a too-frequent
operation of the defrost cycle and a lower than expected
airflow at the outdoor coil. Continued testing of the Insider
in 2002 indicated a 10% increase in COP due to increased
airflow at the outdoor coil. At Vincent Village, the property
manager indicated a high degree of satisfaction with the
Insider heat pumps, with no comfort complaints. Flip flop
testing that varies the compressor and electric resistance
heat were conducted in the WSU and ZEMH. The results of
those tests being analyzed for a ASHRAE paper to be submitted
in 2005. The Insider Flip flop test results are presented
in Figure 34.
Energy Conservatory
BAIHP staff work with the Energy Conservancy (EC) to
evaluate their new products for measuring air handler and
exhaust fan flows. In 2004, BAIHP staff worked with EC
staff to develop an automated test that will provide duct
leakage to outside. Discussion with EC indicated significantly
increased sales of duct blasters to HUD-code manufacturers
as a result of BAIHP efforts. WSU continues to work with
EC to develop new building science tools for HUD-code housing.
Other Technologies
In 2004, BAIHP staff submitted a status report summarizing
program efforts to introduce BAIHP manufacturers to new
technologies. The report highlights the barriers and successes
made regarding:
- 24” OC
Wall Framing
- Air-Tight Can Lighting
Fixtures
- Solar Ready design
- Improved flashing/drainage systems
- High Efficiency
Water Heaters
- Blown Cellulose Hybrid Floor Insulation
- Condensing
Gas Furnaces
- Heat
Pump Water Heaters – Site built
- Hi-R
wall Systems (Foam Sheathing + Icynene) – Site
Built
Research Support
ASHRAE
During
2003, in the capacity of chairing ASHRAE’s
6.2 Technical committee, BAIHP staff directed a major effort
to revise Chapter 9 of the ASHRAE Systems Handbook, “Design
of Small Forced-air Heating and Cooling Systems.” The
revisions to the chapter, which incorporated BAIHP research,
were accepted by the committee, and forwarded to ASHRAE
for publication. In 2004 BAIHP staff provided assistance
to other BA teams to improve chapter 43 of the ASHRAE Applications
Handbook – Envelopes.
BAIHP staff have also participated in ASHRAE research
projects, conferences, symposiums, seminars and forums,
including:
- Authoring a paper on duct leakage, which was submitted
and approved for presentation at ASHRAE summer meeting
in 2004.
- Making
a presentation at the ASHRAE summer meeting in 2003, “Uncontrolled
Air Flow in Small Commercial Buildings.”
- Moderating
a forum on HVAC experiences in HUD code housing at
ASHRAE’s summer meeting in 2002. 20
industry and building science professionals participated
in the forum.
- Co-chairing
ASHRAE’s Technical Committee 6.3 – Residential
Forced Air Heating and Cooling Equipment, which is responsible
for ASHRAE standard 152 – Thermal Distribution
Systems.
- Building America research on ductwork and HVAC systems
will be included in the next version of the ASHRAE standards.
Building America research will also be a part of future
efforts in TC 6.3.
NFPA-501
BAIHP continues to support the NFPA standards process.
The NFPA standard is typically incorporated into the HUD
code, which governs the construction of over 250,000 HUD
code homes each year.
- In 2003, BAIHP staff integrated BAIHP duct leakage
and cost data into proposals to the NFPA-501 committee.
Based on this data, NFPA approved a new standard on duct
tightness, as well as a refined duct testing protocol.
- In 2002, BAIHP staff cited Building America research
and demonstration efforts in support of additional successful
proposals for standards revision, including duct testing,
and use of mastic in duct sealing.
ACEEE
- BAIHP
staff have co-authored two papers presented at ACEEE
Conferences, “Pushing the Envelope: A
Case Study of Building the First Manufactured Home Using
Structural Insulated Panels,” and “Washington
State Residential Ventilation and Indoor Air Quality
Code (VIAQ) - Whole House Ventilation Systems Field Research
Report.”
- In 2004, BAIHP staff coordinated 24 peer reviewed
papers for the Residential technologies track at the
Summer Study and coordinated informal sessions on HUD-code
housing.
National Institute of Standards and Technologies
(NIST)
BAIHP staff continues to work with NIST staff and industry
representatives to evaluate ventilation and IAQ issues
in HUD code homes.
- BAIHP staff also worked with NIST and the Energy Conservancy
to perform tests on a typical HUD code model house on
the NIST campus in Gaithersburg, Maryland. Testing indicates
low flow rates of the whole house ventilation system
and significant duct leakage.
- In 2004, discussions with NIST, LBL, Ecotope and Energy
Conservatory continued on a retrofit research effort
with Dupont Tyvek, and development of new ventilation
system controls with Panasonic. These discussions will
continue.
National Manufactured Housing Research Alliance (MHRA)
BAIHP
staff continues to participate on MHRA’s
ENERGY STAR committee, which is developing Quality Assurance
procedures with USEPA on ENERGY STAR manufactured homes.
An article on the ZEMH appeared in the MHRA newsletter.
WSU worked with MHRA to provide an article on the ZEMH
project. WSU continues to provide technical support to
MHRA on ENERGY STAR and other building science/energy related
efforts such as the MHI roadmap.
|