Building
thermal conditions and air conditioning power usage were
obtained. The attic temperature during the peak summer hour
is 40oF greater than ambient air temperature
in the control home while no greater than ambient with highly
reflective roofing systems. Light colored shingles and terra
cotta roofs show temperatures in between those extremes.
Measurements
showed that the three white reflective roofs would reduce
cooling energy consumption by 18-26% and peak demand by
28-35%. The terra cotta tile roofs and white shingles would
produce cooling savings of 3-9% and 3-5%, respectively,
while the sealed attic construction with an insulated roof
deck would produce reductions of 6-11%.
Introduction
Traditional architecture in hot climates has long recognized
that light building colors can reduce cooling loads (Langewiesche,
1950; Givoni, 1976). A series of simulation and experimental
studies have demonstrated that building reflectance can
significantly impact cooling needs (Givoni and Hoffmann,
1968; Taha et al., 1988; Griggs and Shipp, 1988, and Bansal
et al., 1992). Full building field tests in Florida and
California using before-after experiments have examined
the impact of reflective roofing on air conditioning (AC)
energy use. In Florida tests measured AC electrical
savings averaged 19% (7.7 kWh/Day) (Parker et al., 1998).
Even greater fractional savings have been reported for similar
experiments in California (Akbari, et al., 1992). Beyond
roof reflectance, additional research has shown that other
approaches such as tile roofs and unvented attics with insulation
under the roof itself, can produce cooler attics resulting
in energy improvements, but of unknown comparative magnitude
(Beal and Chandra, 1995; Rudd, 1998; Rudd et al., 2000).
Duct
systems are often located in the attic space in Sun Belt
homes with slab on grade foundations. In an early assessment
of the impact of reflective roofing, infrared thermo-graphy
revealed that heat gain to attic-mounted duct systems and
air handlers are adversely affected by hot attics (Parker
et al, 1993B). As shown in Figure 1, previous analysis has
shown that attic heat gain to the thermal distribution system
can increase residential cooling loads by up to 30% during
peak summer periods (Parker et al., 1993; Jump et al, 1996).
Further benefits arise from the reduction of attic air temperature
and its impact on ceiling insulation conductivity (Levinson
et al., 1996).
|
Figure
1.
Vented Attic Thermal Processes and Interaction with
Duct Heat Gain |
Research
Description
While
previous research efforts have investigated the thermal
performance of various roofing systems, this particular
study represents the first time an attempt has been made
to quantify roofing influence on cooling performance on
identical, unoccupied, side-by-side residences. The project
consisted of seven, single-family residential homes located
in Ft Meyers, Florida. The focus of the study was to investigate
how various roofing systems impact air conditioning electrical
demand. All seven residences had a three bedroom,
one bath floor plan and were of identical construction and
exposure. The houses underwent a series of tests in order
to ensure that the construction and mechanical systems performed
similarly. The sites were given a three-letter code to describe
each roofing system:
- Dark
gray fiberglass shingles (RGS)
-
White barrel-shaped tile (RWB)
-
White fiberglass shingle (RWS)
- Flat
white tile (RWF)
- Terra
cotta barrel-shaped tile (RTB)
- White
5-vee metal (RWM)
- Sealed
attic with insulation on the roof plane (RSL)
Monitoring
collected 15-minute data on comparative performance of the
seven homes in the summer of 2000 under unoccupied and carefully
controlled conditions for a month. Relevant construction
details are summarized in Table 1.
Table
1. Construction Characteristics for Research Homes
Floor
area: |
1144
ft2 (conditioned) |
Net
Wall area: |
770
ft2 |
Window
area: |
101
ft2; six single glazed units with light
gray tint
- 45
ft2 facing east (3 units)
- 40
ft2 facing south (2 units)
- 15
ft2 facing west (1 unit)
|
Ceiling: |
1144
ft2 |
Doors: |
40
ft2; 2 doors (one to unconditioned garage). |
Overhang: |
2
ft around entire perimeter |
Ceiling
Insulation: |
R-19
(blown cellulose) |
Wall
Insulation: |
R-14
(fiberglass batts R-11 with R-3 sheathing) |
Wall
Construction: |
Wood
frame (16 inches on center) |
Roof
Construction: |
Hip
roof, 18.4 degree pitch (0.15 framing fraction) |
Foundation |
Uninsulated,
concrete slab on grade |
Roofing
Solar Reflectance
Laboratory
reflectance measurements were taken on each of the evaluated
roofing materials (Table 2). Reflectivity is the fraction
of total incident solar radiation reflected by a surface.
Table
2. Laboratory Measured Solar Reflectances of Utilized
Roofing Materials
|
%
Solar Reflectance |
Dark
gray shingle (RGS, RSL) |
8.2 |
White
shingle (RWS) |
24.0 |
Terra
Cotta barrel tile (RTB) |
34.6 |
White
barrel tile (RWB) |
74.2 |
Flat
white tile (RWF) |
77.3 |
White
metal (painted)* (RWM) |
66.2 |
Sealed
Attic Construction RSL
The
seventh house (RSL) tested a new approach to residential
insulation: an attic completely sealed and with a spray
foam insulation applied to the underside of the roof decking
in place of conventional blown or batt insulation. The scheme
insulates at the roof decking rather than at the surface
of the living space ceiling. Two primary advantages are
significantly less duct heat load within the attic space
as well as reduced humidity and infiltration. Research has
shown this as a promising construction technique (Rudd and
Lstiburek, 1998; et al., 2000) in a series of production
homes in Las Vegas, Nevada and Tucson, Arizona.
One
potential disadvantage is that the roof insulation can result
in significantly higher decking and roof surface temperatures.
Also, the insulation at the roof deck has a more difficult
task since it is working against 170o (temperature
of roofing) rather than 130o (temperature on
top of insulation in a conventional attic at summer peak).
The ducts are exposed to less heat gain, but building heat
transfer surface areas are increased relative to the conventional
case.
The
roofing system on the RSL home was identical to that in
the control home, dark gray composition shingles over roofing
felt and decking. The external appearance was like the conventional
homes, however foam insulation was used in the roof deck
rather than cellulose insulation in the ceiling assembly.
The attic floor consisted solely of rafter and ½
inch gypsum board. The roof deck of the RSL was covered
with 5 inches of insulating foam. Application thickness
was targeted to achieve an R-19 application – similar
in thermal resistance to the cellulose insulation in the
other homes. The installed product is a semi-rigid polyurethane
foam insulation with a nominal density of 0.45 - 0.5 lbs/ft3
and an R-value of 3.81 ft2-hr- oF/Btu/inch.
The product also claims to help improve air sealing of the
home by controlling leakage from building joints.
Calibrating
Thermostats and Influence of Set Temperature
Since variation in interior thermostat temperature was known
to be a large variable controlling differences in space
cooling, special effort was made to carefully adjust the
thermostats in each home so that each was closely maintaining
the same interior temperature. This was done using thermocouples
which measured the temperature in a central hallway by the
thermostat, but not overly close to it due to the heat emitted
from the electronics within the digital thermostat.
To
evaluate the impact of thermostat set temperature the thermostats
were adjusted up one oF for four days at the
end of the project before the homes were occupied. The typical
increase was from 77o to 78o. These
data were used to examine how the thermostat set-up influenced
cooling in order to properly adjust project results. This
was accomplished by searching for days in the set-up period
having similar weather conditions. As expected the impact
was greatest on the cooler days where the outdoor temperature
approached the thermostat set temperature and solar radiation
impacts were minimized. Over the comparison, space cooling
decreased by an average of 12.1% per oF that
the temperature was increased. When confined only to the
peak day, the impact was 8.3% per oF.
Results
over the Monitoring Period
The
relative performance of the homes over the entire unoccupied
monitoring period was evaluated. The five figures below
(Figures 2-6) show the fundamental impacts of the roofing
system on cooling energy consumption over the entire unoccupied
monitoring period from July 8th - July 31st,
2000.
Figure
2 depicts the ambient average air temperature and solar
conditions over the entire unoccupied period. Figures 3,
4 and 5 show the thermal influences of the roofing system.
The first plot graphs the average roof surface temperature
over the daily cycle. The second plot shows the corresponding
temperature at the underside of the roof decking surface.
Note that the roof surface temperature and decking temperature
are highest with the sealed attic construction since the
insulation under the decking forces much of the collected
solar heat to migrate back out through the shingles. On
average the shingles reach a peak temperature that is seven
degrees hotter than standard construction. However, decking
temperatures run almost 20oF hotter. The white
roofing systems (RWM, RWF and RWB) experience peak surface
temperatures approximately 20oF lower than darker
shingles. The terra cotta barrel tile case runs about 10o
cooler.
The
measured mid attic air temperatures (Figure 5) above the
ceiling insulation revealed the impact of white reflective
roofs with average peak temperatures approximately 20o
cooler than at the control home. Whereas the attic in the
control home reaches 110oF on the typical day,
the attics with the highly reflective white roofing materials
only rise to about 90oF. Figure 6 shows the clear
relationship between peak daily air temperature and attic
temperature for the differing roofing systems.
|
Figure
5. Average Attic Air Temperature Profiles
over the Unoccupied Period |
|
Figure
6.
Relationship of Daily Peak Air to Peak Attic Temperature |
As
expected, the home with the sealed attic had the lowest
attic temperatures reaching a maximum of 83oF
compared with the 77oF being maintained inside.
However, the sealed attic case has no insulation on the
ceiling floor with only studs and sheet rock. Thus, from
a cooling loads perspective, the low attic temperature with
this construction is deceptive. Since ½ inch sheet
rock only has a thermal resistance of 0.45 hr-ft2-oF/Btu,
a significant level of heat transfer takes place across
the uninsulated ceiling. While this construction method
reduced attic air temperatures, it did not reduce ceiling
heat transfer as well as other options. Ceiling heat
fluxes are actually higher. In this case, the ceiling and
duct system is unintentionally cooling the attic space which
can lead to the false impression that roof/attic loads are
lower.
Figure 7 summarizes the measured cooling load profiles for
the seven homes over the unoccupied monitoring period. Not
surprisingly, the control home has the highest consumption
(17.0 kWh/day). The home with the terra cotta barrel tile
has a slightly lower use (16.2 kWh/day) for a 5% cooling
energy reduction. Next is the home with the white shingles
(15.6 kWh/day) – an 8% reduction. The sealed
attic comes in with a 12% cooling energy reduction (14.9
kWh/day).
|
Figure
7.
Average Space Cooling Energy Demand Profiles over the
Unoccupied Period |
The
true white roofing types (> 60% reflectance) clearly
show their advantage. Both the white barrel and white flat
tile roofs averaged a consumption of 13.3 kWh/day or a 22%
cooling energy reduction, while the white metal roof shows
the largest impact with a 12.2 kWh/day August consumption
for a 28% reduction. The numbers in Table 3 are adjusted
to account for differences in interior temperature and AC
performance:
Table
3. Cooling Performance During Unoccupied Period: July
8th - 31st, 2000
Site |
Total
kWh |
Savings
kWh |
Save
% |
Thermo-
stat |
Avg.
Attic
oF |
Max.
Attic
oF |
Temp.
Adjust.
% |
Adjust
Sav.
% |
Field
EER |
Final
Sav.
% |
RGS |
17.03 |
0.00 |
0.0 |
77.15o |
90.8 |
135.6 |
0.0 |
0.0 |
8.30 |
0.0 |
RWS |
15.29 |
1.74 |
10.2 |
77.03o |
88.0 |
123.5 |
-1.2 |
11.4 |
9.06 |
10.6 |
RSL |
14.73 |
2.30 |
13.5 |
77.69o |
79.0 |
87.5 |
5.4 |
8.1 |
8.52 |
7.8 |
RTB |
16.02 |
1.01 |
5.9 |
76.99o |
87.2 |
110.5 |
-1.6 |
7.5 |
8.12 |
7.7 |
RWB |
13.32 |
3.71 |
21.8 |
77.43o |
82.7 |
95.6 |
2.8 |
19.0 |
8.49 |
18.5 |
RWF |
13.20 |
3.83 |
22.5 |
77.36o |
82.2 |
93.3 |
2.1 |
20.4 |
7.92 |
21.5 |
RWM |
12.03 |
5.00 |
29.4 |
77.64o |
82.9 |
100.7 |
4.9 |
24.5 |
8.42 |
24.0 |
It is noteworthy that the average July temperature during
the monitoring period (81.6oF) was very similar
to the 30-year average for Ft. Myers (82oF).
Thus, the current data are representative of typical South
Florida weather conditions. Relative to the standard control
home, the data show two distinct groups in terms of performance:
- Terra
Cotta tile, white shingle and sealed attic constructions
produced approximately an 8-11% cooling energy reduction
- Reflective
white roofing gave a 19-24% cooling energy reduction.
White
flat tile performed slightly better than the white barrel
due to its greater reflectance. The better performance of
white metal appears to come from the fact that lower nighttime
and early morning attic temperatures are achieved than those
for tile or shingles, leading to lower nighttime cooling
demand.
Peak
Day Performance
July 26th was one of the hottest and brightest
days in the data collection period and was used to evaluate
peak influences. Average solar irradiance was 371 W/m2
and maximum temperature was 93.0oF. These data
show that during periods of high solar insolation the performance
of the sealed attic case (RSL) suffers significantly. Decking
and attic temperatures are illustrated in Figures 8 and
9. For instance, both the tile roof and white shingle did
better at controlling demand than the sealed attic on this
very hot day. The white metal roof did best on the hottest
day although not appreciably different from the other white
roofing types. Also, the savings for the white roofs relative
to the control were greater than for other days.
Table
4. Summer Peak Day Cooling Performance: July 26th,
2000
Site |
Cooling
Energy |
Savings |
Peak
Period* |
kWh |
Percent |
Demand
(kW) |
Savings
(kW) |
Percent |
RGS |
18.5
kWh |
|
---- |
1.631 |
0.000 |
---- |
RWS
|
16.5
kWh |
2.0 |
11% |
1.439 |
0.192 |
11.8% |
RSL
|
16.5
kWh |
2.0 |
11% |
1.626 |
0.005 |
0.3% |
RTB
|
17.2
kWh |
1.3 |
7% |
1.570 |
0.061 |
3.7% |
RWB
|
13.4
kWh |
5.1 |
28% |
1.073 |
0.558 |
34.2% |
RWF |
14.2
kWh |
4.3 |
23% |
1.019 |
0.612 |
37.5% |
RWM
|
12.4
kWh |
6.1 |
33% |
0.984 |
0.647 |
39.7% |
|
Figure
8. Roof Decking Temperature Profiles for
July 26, 2000 |
|
Figure
9. Attic Temperature Profiles for July 26,
2000 |
Analysis
of Energy Savings
We calculated the annual cooling energy savings of the differing
roofing materials by two methods. First we estimated the
normalized daily average reduction in cooling kWh from each
construction and then multiplied this quantity by one over
the fraction of average cooling which takes place in the
month of July. The normalized savings are the values in
Table 5 incorporating correction factors for air conditioner
performance and interior temperature differences.
The
fraction of space cooling in the month of July was obtained
from averaged empirical monitoring results from a large
sample of homes metered by the utility. These data show
that 15.6% of total annual cooling in the South region occurs
in the month of July. Total average cooling there for the
month is 1,141 kWh or about 36.8 kWh/day. Since the homes
in the Habitat study are only about 60% of the average size
of a typical new home, we suggest that savings be indexed
by the size of the ceiling against that in the study (1,144
ft2).
Table
5 Annual Cooling Energy
Savings from Empirical Measurements
Site |
Measured
kWh/Day |
Temp
Correction
AC
Correction |
kWh
Day
Estimate |
Savings
(kWh/day) |
Annual
Savings
kWh* |
RGS |
17.03 |
1.000
/ 1.000 |
17.03 |
0.00 |
0 |
RWS |
15.29 |
0.988
/ 1.092 |
16.49 |
0.54 |
110 |
RSL |
14.73 |
1.054
/ 1.027 |
15.94 |
1.09 |
223 |
RTB |
16.02 |
0.984
/ 0.978 |
15.42 |
1.60 |
329 |
RWB |
13.32 |
1.021
/ 0.954 |
14.01 |
3.02 |
618 |
RWF |
13.20 |
1.049
/ 1.014 |
12.86 |
4.17 |
852 |
RWM |
12.03 |
1.028
/ 1.023 |
12.80 |
4.23 |
864 |
*
The estimate is based on a ratio of 6.59 for South (1/0.1517
for 15.17% of cooling in July). House size assumptions must
be accounted for when estimating average savings or those
for a specific case.
An
alternative calculation was made using daily regression
results. The independent parameters are the daily air temperature
and average solar radiation (global horizontal irradiance)
that are used to estimate the daily average kWh at that
temperature and irradiance value. The regressions for each
home are then applied to Typical Meteorological Year (TMY)
data for Miami, Florida. The results shown in Table 6 become
the estimated space cooling use for each construction. Savings
are then normalized by the temperature, air conditioner
performance corrections and house size to yield final estimates.
Table
6. Annual Cooling Energy Savings from Regression Analysis
Method
Site |
kWh |
kWh
Savings (*) |
RGS |
3679 |
0 |
RWS |
3471 |
208
(191) |
RSL |
3242 |
437
(404) |
RTB |
3570 |
109
(113) |
RWB |
2809 |
870
(893) |
RWF |
2859 |
820
(771) |
RWM |
2584 |
1095
(1041) |
(*)
Normalized to correct for off-reference temperature and
AC performance.
Peak
Demand Reduction
Summer
peak demand savings were also estimated in two ways. First
we used the measured demand of the seven houses between
the hours of 4 and 6 PM on the peak day (July 26, 2000).
This estimate should be indexed to the ceiling area for
typical houses. Considering that the typical Florida home
likely has a ceiling area averaging about 1770 square feet,
the ratio of the impact would be approximately 55% greater
than that estimated here (1,144 ft2 ceiling).
This also better fits the average cooling energy demand
from end-use studies from the utility that show a summer
peak AC demand of approximately 2.9 kW in occupied homes.
Our monitoring study showed an average peak demand of 1.63
kW in the control home. The average peak demand for the
study sites (based on the peak data for July 26th)
are reproduced previously in Table 4.
The second method of estimating demand reductions used hourly
regression equations. To estimate peak impacts, the regressions
were evaluated at an outdoor temperature of 92oF
- which is close to the peak design temperature at 5 PM.
The
regression analysis method estimates in Table 7 show higher
peak demand impacts. Demand reduction for the sealed attic
construction is very small (<0.2 kW) whereas white shingle
and terra cotta tile roof produce a demand reduction of
0.4 - 0.5 kW. The white highly reflective roofing systems
produced demand reductions of 0.8 - 1.0 kW.
Table
7. Regression Estimated Cooling Peak Demand in Research
Homes
Site |
Demand
kW |
Reduction
kW |
Demand
Reduction+
kW |
Demand
Reduction
% |
RGS |
1.788 |
0.000 |
0.00 |
0.0% |
RWS |
1.480 |
0.308 |
0.48 |
17.2% |
RSL |
1.701 |
0.087 |
0.13 |
4.9% |
RTB |
1.558 |
0.230 |
0.36 |
12.9% |
RWB |
1.197 |
0.591 |
0.92 |
33.0% |
RWF |
1.153 |
0.635 |
0.98 |
35.5% |
RWM |
1.278 |
0.510 |
0.79 |
28.5% |
+
Normalized to 1,770 ft2 typical home.
Simulation
Analysis
FSEC has developed a hourly building energy software, EnergyGauge
USA, which runs based on the DOE-2.1E simulation engine.
A key new component in this software explicitly estimates
the performance of attics and the interactions of duct systems
if located there. In Florida homes, ducts are almost always
in the attic space and previous analysis shows that under
peak conditions, the cooling system can lose up to 30% of
its cooling capacity through heat transfer with the hot
attic (Parker et al., 1993). The software has previously
been used to estimate the impact of reflective roofing around
the U.S. (Parker et al., 1998). It has been field validated
in estimating the space cooling energy use of three homes
in Ocala, Florida.
We
created detailed input descriptions of each of the 1,114
ft2 Habitat homes in the study (including the
shading impacts of surrounding buildings) and simulated
their performance to see how closely the simulation could
match the measured results. Table 8 shows the results.
Table
8. Simulation Analysis Results
Building
Site |
Annual
Cooling
(kWh) |
Cooling
Savings
(kWh) |
July
Cooling
kWh
(kWh/D) |
Peak
Cooling Demand |
(kW) |
Reduction |
RGS |
2,666 |
---- |
503
(16.2) |
1.61 |
---- |
RWS |
2,549 |
117 |
484
(15.6) |
1.51 |
0.10 |
RSL |
2,646 |
20 |
493
(15.9) |
1.42 |
0.19 |
RTB |
2,450 |
216 |
467
(15.1) |
1.30 |
0.31 |
RWB |
2,211 |
455 |
427
(13.8) |
1.17 |
0.44 |
RWF |
2,191 |
475 |
424
(13.7) |
1.18 |
0.43 |
RWM |
2,281 |
385 |
441
(14.2) |
1.39 |
0.22 |
We
noted that the simulation predicts very similar absolute
values to the measured space cooling at the sites, although
predicted savings are somewhat less than those measured.
Both the monitoring and simulation shows the white roofing
types to provide the greatest savings and peak demand impact,
followed by the tile roof, white shingle and sealed attic
construction.
Conclusions
Roof and attic thermal performance exerts a powerful influence
on cooling energy use in Florida homes. Unshaded residential
roofs are heated by solar radiation during the daytime hours
causing high attic air temperatures. The large influence
on cooling demand is due both to the impact on ceiling heat
transfer as well as heat gains to the duct systems which
are typically located in the attic space with slab on grade
construction.
With
the described project we tested six side-by-side Habitat
homes in South Florida with identical floor plans and orientations
using different roofing systems designed to reduce attic
heat gains. A seventh house with an unvented attic and insulated
roof deck was also included in the test.
The
data showed that solar heating had a large effect on attic
thermal performance in the control home. Air conditioning
data were also collected allowing characterization of the
impact on cooling energy use and peak electrical demand.
Each of the examined alternative roofing systems were found
to be superior to standard dark shingles, both in providing
lower attic temperatures and lower AC energy use. The sealed
attic construction provided modest savings to cooling energy,
but no real peak reduction due to its sensitivity to periods
with high solar irradiance. Our research points to the need
for reflective roofing materials or light-colored tile roofing
for good energy performance with sealed attics.
Our project revealed essentially two classes of performance
for the 1,144 square foot homes. Analysis by two methods
showed the white highly reflective roofing systems (RWF,
RWB and RWM) provide annual cooling energy reductions of
600-1,100 kWh in South Florida (18-26%). Savings of terra
cotta tile roofs are modest at 3-9% (100-300 kWh), while
shingles provide savings of 3-5% (110-210 kWh). Sealed attic
construction produced savings of 6-11% (220-400 kWh). The
highly reflective roofing systems showed peak demand impacts
of 28-35% (0.8-1.0 kW). White metal had the best cooling
related performance. Its high conductivity coupled with
nocturnal radiation resulted in lower nighttime and early
morning attic temperatures that lead to a reduced cooling
demand during evening hours.
In
summary, the selection of roof with high solar reflectance
represents one of the most significant energy-saving options
available to homeowners and home builders in hot climates.
Further, the same materials strongly reduce the house peak
cooling demand during utility coincident peak periods -
a highly desirable attribute.
Acknowledgments
Special thanks to Florida Power and Light Company who sponsored
the study and Habitat for Humanity who worked with FSEC
to build the identical test homes.
References
Akbari,
H., Taha, H. and Sailor, D., 1992. "Measured Savings
in Air Conditioning from Shade Trees and White Surfaces,"
Proceedings of the 1992 ACEEE Summer Study on Energy
Efficiency in Buildings, American Council for an Energy
Efficient Economy, Washington D.C., Vol. 9, p. 1.
Bansal,
N.K., Garg, S.N. and Kothari, S., 1992. "Effect of
Exterior Surface Color on the Thermal Performance of Buildings,"
Building and Environment, Permagon Press, Vol. 27,
No. 1, p. 31-37, Great Britain.
Beal,
D. and Chandra, S., 1995. "The Measured Summer Performance
of Tile Roof Systems and Attic Ventilation Strategies in
Hot Humid Climates," Thermal Performance of the
Exterior Envelopes of Buildings VI, U.S. DOE/ORNL/BETEC,
December 4-8, 1995, Clearwater, FL.
Givoni,
B. and Hoffman, M.E., 1968. "Effect of Building Materials
on Internal Temperatures," Research Report, Building
Research Station, Technion Haifa.
Givoni,
B., 1976. Man, Climate and Architecture, Applied
Science Publishers Ltd., London.
Griggs,
E.I, and Shipp, P.H., 1988. "The Impact of Surface
Reflectance on the Thermal Performance of Roofs: An Experimental
Study," ASHRAE Transactions, Vol. 94, Pt. 2,
Atlanta,GA.
Jump,
D.A., Walker, I.S. and Modera, M.P., 1996. "Measurements
of Efficiency and Duct Retrofit Effectiveness in Residential
Forced Air Distribution Systems," Proceedings of
the ACEEE 1996 Summer Study on Energy Efficiency in Buildings,
Vol. 1, p. 147, American Council for an Energy Efficient
Economy, Washington D.C.
Langewiesche,
W., 1950 "Your House in Florida," House Beautiful,
January, 1950, p.74.
Levinson,
R., Akbari, H. and Gartland, L.M., 1996. "Impact of
the Temperature Dependency of Fiberglass Insulation R-Value
on Cooling Energy Use in Buildings," Proceedings
of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings,
Vol. 10, p. 85, American Council for an Energy Efficient
Economy, Washington D.C.
Parker,
D.S., Fairey, P.W. and Gu, L., 1993. "Simulation of
the Effects of Duct Leakage and Heat Transfer on Residential
Space Cooling Energy Use," Energy and Buildings,
20, p. 97-113, Elsevier Sequoia, Netherlands.
Parker,
D.S., McIlvaine, J.E.R., Barkaszi, S.F. and Beal, D.J.,
1993A. Laboratory Testing of the Reflectance Properties
of Roofing Materials, FSEC-CR-670-93, Florida Solar
Energy Center, Cape Canaveral, FL.
Parker,
D.S., Cummings, J.B., Sherwin, J.S., Stedman, T.C. and McIlvaine,
J.E.R., 1993B. Measured Air Conditioning Electricity
Savings from Reflective Roof Coatings Applied to Florida
Residences, FSEC-CR-596-93, Florida Solar Energy Center,
Cape Canaveral, FL.
Parker,
D.S., P. Fairey and L. Gu, 1993. "Simulation of the
Effects of Duct Leakage and Heat Transfer on Residential
Space Cooling Energy Use," Energy and Buildings
20, p. 97-113, Elsevier Sequoia, Netherlands.
Parker,
D.S., Y.J. Huang, J. Sherwin, S.J. Konopacki and L. Gartland,
1998. "Measured and Simulated Performance of Reflective
Roofing Systems in Residential Buildings," ASHRAE
Transactions, Vol. 104, Pt. 1B, January 1998.
Rudd,
Armin F., and Lstiburek, Joseph W., 1998. "Vented and
Sealed Attics in Hot Climates," ASHRAE Transactions,
Vol. 104, Pt. 2, Atlanta,GA.
Rudd,
Armin F., Joseph W. Lstiburek and Kohta Ueno, 2000., "Unvented
Cathedralized Attics: Where We've Been and Where We're Going,"
Proceedings of the 2000 Summer Study on Energy Efficiency
in Buildings, American Council for an Energy Efficient
Economy, Vol. 1, p. 247, Washington D.C.
Taha,
H., Akbari, H., Rosenfeld, A.H. and Huang, J., 1988. "Residential
Cooling Loads and the Urban Heat Island--the Effects of
Albedo," Building and Environment, Vol 23, No.
4, Permagon Press, Great Britain.