HEATING,
VENTILATION AND AIR CONDITIONING (HVAC) SYSTEMS:
Design:
Complete operation protocols and maintenance procedures
shall be provided for all HVAC equipment. Procedures shall
be written to be easily understood and implemented by facilities
managers and teachers. Teacher operable controls shall be
affixed with a permanent label listing control instructions.
Sizing:
Heating systems shall be sized according to standard engineering
practice, using an interior design temperature of 70̊F
and the standard ASHRAE winter design temperature (WDT) for
the building location, or as approved. Cooling systems shall
be sized according to standard engineering practice using
ASHRAE Total Cooling Load calculation procedures (ASHRAE Fundamentals,
Chapter 29).
Heat
Pump Systems: Heat pumps shall have a minimum HSPF of
7.5 and air conditioning systems shall have a minimum SEER
of 12.0
HVAC
Controls: HVAC setback shall occur whenever the classroom
is not occupied (at night, weekends, summer vacations and
holidays). The ventilation system shall be controlled by
an occupancy sensor in conjunction with an on-off switch that
can be accessed by occupants. The occupancy sensor will shut
off the system off 15 minutes after occupancy. The heating
and air conditioning system will be controlled by a 24/7/365
programmable thermostat with a minimum set back of 50 degrees
for heating during unoccupied periods. Thermostats are required
to ensure correct operation for at least three days in the
event of power outages.
Air
conditioning: If both air conditioning and electric heat
are required, a heat pump shall be used as the primary heating/cooling
system.
Economizer:
If air conditioning is not provided, economizer cooling is
required
Ventilation
Rates: Minimum ventilation airflows shall meet the requirements
of ASHRAE Standard 62-1989 and state codes: 15 cfm per person.
Heat
Recovery Ventilation: Heat recovery ventilation is recommended.
Ventilation
Duct Insulation: All ventilation exhaust ducts shall
be insulated to at least R-4.
Outside
Air Source: The outside-air source shall be located at
least ten feet from exhaust vents to minimize drawing outdoor
pollutants and excessive outdoor noise.
HVAC
Ducts: To minimize noise and to provide conditioned air
evenly to all occupants, ventilation and air conditioning
shall be provided through a series of ducts.
Ductwork
for HVAC systems shall be installed to comply with the equipment
manufacturer's static pressure specifications.
Ductwork
shall be sealed using approved sealant as appropriate. Metal
ducts shall be sealed with approved mastic.
Duct
board shall be sealed with mastic or UL181 pressure sensitive
tape applied per UL listing.
Moisture
Vapor Transfer: A vapor retarder of not more than 1.0
perm dry cup rating shall be installed in exterior walls,
exterior ceilings and exterior floors. It shall be installed
according to the manufacturer's specifications on the warm
side (in winter) of all insulation.
Attic
Ventilation: Adequate attic ventilation shall be maintained
above all ceiling insulation by providing both high and low
vents for roof rafter installed insulation, or gable end vents
for insulation installed above a T-bar ceiling.
At
least 1 square foot of net-free vent area shall be provided
for every 300 ft2 of ceiling area with 50 to 60
percent of the vent area located near the roof ridge and 40
to 50 percent located near the eaves. A minimum clearance
of one inch shall be maintained between attic insulation and
the roof sheathing when soffit vents are used.
Exception:
Attic venting is not required when Structural Insulated Panels
(SIP) are used to create an un-vented "hot roof," or an unvented
attic design is used. In the case of the use of SIPs, all
panels shall be effectively sealed together.
General:
The classroom shall be inspected on site to determine compliance
with these specifications and manufacturer's instructions
and/or local codes. An on-site set up guideline checklist
shall be used to meet the following specifications.
Damage
Repair: Damage occurring to factory-installed energy measures
during transportation and setup shall be corrected. Any disturbance
of insulation due to wiring or other on-site work shall be
corrected.
Marriage
Line: The ceiling marriage line shall be sealed using
gasket and non-porous silicon caulking, foam or closed cell
backer rod.
Exception:
The marriage line need not be sealed if the attic ventilation
is provided through roof cap venting, using the rafter marriage
line as the ventilation path. In such a situation, however,
there must be a vapor barrier installed between the T-bar
ceiling and the attic insulation.
The
floor and wall marriage lines shall be inspected to insure
integrity during shipping, and replaced or repaired as necessary.
Window
and Door Frames: Window and door frames shall be installed
and adjusted (if needed) according to the original equipment
manufacturers instructions to minimize air leakage and water
penetration. Windows and doors shall be tested to ensure
that they open and close easily and seal tightly, and confirm
weather-stripping is correctly installed.
Other
Penetrations: All penetrations in the building envelope,
such as for piping, wiring, recessed fixtures in walls and
ceilings, and exhaust-fan housings shall be sealed.
Ground
Cover: A vapor retarder, consisting of 6-mil black polyethylene
or approved linear low-density poly, shall cover the ground
throughout the entire crawl space. All joints shall be lapped
at least 8 inches.
Crawl
Space Ventilation: Crawl space ventilation shall meet
all applicable state or local codes.
HVAC
System:
-
If mechanical dampers are installed, they shall be opened
to the 100% open position, or set to design specifications.
-
A complete maintenance and operation manual shall be provided
to the school facilities manager. The manager shall use
this manual and keep records of M&O for each unit.
Commissioning
ensures the proper functioning of the classroom's mechanical
systems and envelope. Prior to the commissioning process,
all parties should agree on the required tasks. After the
portable classroom is set up on site the commissioning shall
include at least the following items:
-
All mechanical equipment shall operate properly in accordance
with the operation protocol provided by the HVAC manufacturer.
The setback controls shall be set to ensure temperature
setback and ventilation system shut down during nights,
weekends, holidays and summer vacations. If provided, the
24/7/365 programmable thermostat shall be programmed for
set back for nights, weekends, holidays and summer vacations.
-
Outside fresh air supply flow measurements shall be taken
to ensure that the correct mechanical ventilation rate is
provided at the appropriate outside damper settings. Exhaust
air flow measurements shall be taken to ensure correct ventilation
system flow rates are achieved if exhaust ventilation is
employed as part of the ventilation system.
- Supply
air-flow measurements shall be conducted to ensure the correct
ventilation air-flow rates of 15 cfm per designed occupancy.
- If
provided, exhaust fan air flow rates shall be tested.
- During
each classroom installation, the first representative classrooms
shall be blower door and duct leakage tested to the values
provided in the prescriptive path. Additional testing is
required until prescriptive path values are achieved.
|