Publication
Index:
Executive
Summary
Over the past 10 years, researchers at the Florida Solar Energy
Center (FSEC) have worked with the Manufactured Housing industry
under the auspices of the U.S. Department of Energy (DOE)
funded Energy Efficient Industrialized Housing Program and
the Building America (BA) Program (www.buildingamerica.gov).
FSEC serves as the prime contractor for DOE’s fifth
Building America Team: the Building America Industrialized
Housing Partnership (BAIHP) which can be found online at:
www.baihp.org.
Data
and findings presented here were gathered between 1996 and
2003 during 39 factory visits at 24 factories of six HUD Code
home manufacturers interested in improving the energy efficiency
their homes. Factory observations typically showed that building
a tighter duct system was the most cost effective way to improve
the product’s energy efficiency.
BAIHP
and others recommend keeping duct system leakage to the outside
(CFM25out) equal to 3% of the conditioned floor area, termed
Qnout. However, most homes seen in a factory setting cannot
be sealed well enough to perform a CFM25out test. Results
of many field tests suggest that CFM25out will be roughly
50% of total leakage (CFM25total). Thus, to achieve a Qnout
of less than 3%, manufacturers should strive for a CFM25total
of less than 6% of the conditioned area (Qntotal).
Researchers measured total duct leakage and/or duct leakage
to the outside in 101 houses representing 190 floors (single
wide equals one floor, double wide equals two floors, etc.).
Ducts systems observed in these tests were installed either
in the attic (ceiling systems) or in the belly (floor systems).
Researchers tested 132 floors with mastic sealed duct systems
and 58 floors with taped duct systems.
Of
the 190 floors tested by BAIHP, the results break down thus:
For mastic sealed systems (n=132), average Qntotal=5.1% (n=124)
with 85 systems achieving the Qntotal = 6% target (68%). Average
Qnout=2.4% (n=86) with 73 systems reaching the Qnout = 3%
goal (85%). For taped systems (n=58), average Qntotal=8.2%
(n=56) with 19 systems reaching the Qntotal = 6% target (34%).
Average Qnout=5.7% (n=30), more than double the mastic average,
with 5 systems reaching the Qnout = 3% goal (17%).
The
results show that, while it is possible to achieve the BAIHP
Qn goals by using tape to seal duct work, it is far easier
to meet the goal using mastic. What isn’t illustrated
by the results is the longevity of a mastic sealed system.
The adhesive in tape can’t stand up to the surface temperature
differences and changes or the material movement at the joints
and often fails. Mastic provide a much more durable seal.
Typical
factory visits consist of meeting with key personnel at the
factory, factory observations, and air tightness testing of
duct systems and house shells. A comprehensive trip report
is generated reporting observations and test results, and
pointing out opportunities for improvement. This is shared
with factory personnel, both corporate and locally. Often,
a factory is revisited to verify results or assist in the
implementation of the recommendations.
- The
most commonly encountered challenges observed in the factories
include:
-
Leaky supply and return plenums
- Misalignment
of components.
-
Free-hand cutting of holes in duct board and sheet metal.
-
Insufficient connection area at joints.
- Mastic
applied to dirty (sawdust) surfaces.
-
Insufficient mastic coverage.
-
Mastic applied to some joints and not others.
-
Loose strapping on flex duct connections.
-
Incomplete tabbing of fittings.
-
Improperly applied tape
Duct
system recommendations discussed in this report include:
-
Set duct tightness target Qn equal to or less than 6% total
and 3% to outside.
-
Achieve duct tightness by properly applying tapes and sealing
joints with mastic
- Accurately
cut holes for duct connections
-
Fully bend all tabs on collar and boot connections
- Trim
and tighten zip ties with a strapping tool
-
Provide return air pathways from bedrooms to main living
areas
Summary
of BAIHP Approach to Achieving Tight Ducts in Manufactured
Housing:
- Set
goal with factory management of achieving Qnout<=3% using
Qntotal<=6% as a surrogate measurement while houses are
in production.
-
Evaluate current practice by testing a random sample of
units
-
Report Qntotal and Qnout findings; make recommendations
for reaching goals
-
Assist with implementation and problem solving as needed
-
Evaluate results and make further recommendations until
goal is met
-
Assist with development of quality control procedures to
ensure continued success
Finally,
duct tightness goals can be achieved with minimal added cost.
Reported costs range from $4 to $8. These costs include in-plant
quality control procedures critical to meeting duct tightness
goals.
Achieving
duct tightness goals provides benefits to multiple stakeholders.
Improving duct tightness diminishes uncontrolled air (and
moisture) flow, including infiltration of outside air, loss
of conditioned air from supply ducts, and introduction of
outside air into the mechanical system. Uncontrolled air flow
is an invisible and damaging force that can affect the durability
of houses, efficiency and life of mechanical equipment, and
sometimes occupant health. With improved duct tightness, manufacturers
enjoy reduced service claims and higher customer satisfaction,
while homeowners pay lower utility bills, breathe cleaner
air, and have reduced home maintenance.
Continue
to Building America Partnership >> |