Publication
Index:
Appendix
B: Duct Leakage and House Pressure Concepts
In
their most basic configuration, forced air central heating
and cooling systems circulate air through a distribution system
that includes a return duct, an air handler, and a supply
duct network. Conditioned air from the house is drawn into
the return duct by a fan in the air handler. The fan pushes
the conditioned return air over a heating or cooling coil
in the air handler. After passing over the coil, air flows
through supply ducts to the various supply registers throughout
the house where it reenters the conditioned space.
Ideally,
the same amount of conditioned air is removed from the house
(via the return duct) that is put back in the house (via the
supply ducts): volume of return air should be equal to the
volume of the supply air. When there is an imbalance, a positive
or negative pressure with respect to the outdoors will result.
This is true for individual rooms also. If more air is being
supplied to a room than is being removed, a positive air pressure
(with respect to adjacent spaces, such as the main body of
the house) will result. Vice versa, if more air is being removed
from a room than is being supplied, a negative pressure (with
respect to adjacent spaces) will result.
Extra
energy is used to condition outside air in both situations.
When rooms or whole houses are pressurized or depressurized,
air will move through small cracks and holes to equalize the
air pressure. A pressurized room is like a balloon with a
small hole. Air is pressing out all sides and seeping through
even the smallest break in the air barrier. In a house, this
might mean that warm moist air is being pushed into the exterior
wall cavity, toward the cold backside of the exterior wall
finish. A depressurized room will pull air in from outside
bringing outside air in contact with the backside of interior
finishes. The resulting conditions may support mold growth,
condensation, rot, or material wetting. Thus, the implications
of duct leakage range from energy efficiency, to health, durability,
and safety.
Air
Distribution System Components and Joints
In a 2002 study conducted by the Florida Solar Energy Center,
69 new, installed air handler cabinets were tested and found
to have an average leakage of 20.4 cfm when under a 25 pascal
pressure difference (Q25, similar to CFM25). This includes
return and supply side leaks. Average leakage at the joint
between the air handler and supply plenum was 1.6 cfm Q25
and at the joint between the air handler and the return plenum
was 3.9 cfm Q25. These numbers pale in comparison to the leakage
measured in the 20 full duct systems tested: average Q25,Supply
of 53 cfm, Q25,Return of 134 cfm, for a Q25Total 187 (Cummings,
et al, 2002).
In
these 20 homes, the full duct system leakage exceeds the air
handler leakage (including plenum connections) an average
of 13 to 1. Also note that the return duct leakage exceeded
supply duct leakage 3 to 1.
Though
ducts and plenums are made of continuous, virtually leak free
materials such as foil backed duct board, sheet metal, and
sleeved flex duct, they consistently leak. Though flex duct
is vulnerable to puncturing, this can not explain the tremendous
leakage occurring in even new duct systems. The explanation
lies in the fabrication joints and the connections between
components.
Joints
between ducts are part of the air barrier and have historically
been sealed with duct tapes. UL 181 approved tapes are still
in use today. An alternative method of sealing duct joints
combines the tensile strength of fiberglass mesh and the elasticity
of mastic. The seal created by mesh and mastic enjoys a more
durable, longer life than the seal formed by tape.
Primary
Leakage Points
Most new homes have a single central return with a return
grill or a simple return system with far fewer inlets than
supply registers. Supply registers are commonly scattered
throughout the house to spread conditioned air evenly through
the space. Between the return grill and the supply register,
there are a multitude of joints and connections presenting
possible leakage sites. The following list of common duct
system joints combines elements of different types of systems
and materials common in the manufactured housing industry:
Ceiling
Systems
Return grill to dry wall (sheet metal/duct board)
Return grill to return plenum (sheet metal/duct board)
Return plenum (sheet metal/duct board) to air handler or drop
out to package unit
Air handler cabinet joints
Supply plenum (sheet metal/duct board) to air handler
Supply plenum (sheet metal/duct board) to main trunk line(s)
(flex)
Main trunk lines to flex collars
Flex collars to supply ducts, both ends (flex)
Flex collar to supply boot (duct board)
Supply boot to drywall
Supply boot to supply register
Supply register to drywall
Floor
Systems
Return grill to dry wall
Return grill to return plenum (sheet metal/duct board)
Return plenum (sheet metal/duct board) to air handler
Air handler cabinet joints
Supply plenum (sheet metal/duct board) to air handler
Supply plenum (sheet metal/duct board) to main supply trunk
line(s) (sheet metal/duct board)
Main trunk line(s) (sheet metal/duct board) to floor riser
or collar
Floor riser (sheet metal) to sub-floor (In-line floor system)
Collar to branch duct (sheet metal/flex) (Perimeter floor
system)
Branch duct (flex/sheet metal) to collar
Collar to floor riser/supply boot (sheet metal)
Riser/supply boot (sheet metal) to subfloor
In
addition to these joints, all the surfaces of all the components
in the air distribution path should be free of holes, tears,
cracks, punctures, gaps, etc. This includes the fabrication
seams in the components. The entire inside of the duct system
from the return air inlet to each supply air outlet* should
be an air tight, planned air flow path.
A
note about return air paths
An additional factor contributing to unbalanced house pressures
include inadequate return air paths from bedrooms. This creates
positive pressure in the bedrooms when the bedroom door is
closed and air is trapped. At the same time, a negative pressure
results in the main body of the house as the air handler continues
to draw the same amount of return air from the open part of
the house. Thus infiltration is induced in the main body,
while exfiltration is induced in the closed room(s). Though
this is not a direct result of duct leakage, it is a result
of having a central return rather than a ducted return from
each private room. Methods of overcoming the limitation of
return air from bedrooms include providing ducted passive
return paths (jump ducts or saddle ducts) or through wall
passages (high-low vent or over door) for return air to move
from bedrooms to the air handler. In diagnostic testing, BAIHP
has documented the impact of this phenomenon on house pressure,
resulting in recommendation to balance supply and return air
into private rooms using passive devices such as through wall/door
grills, high-low wall grills, jump ducts (also called saddle
ducts), or individual return grills ducted to a central return
plenum.
Continue
to Appendix C - Letters from Manufacturers Regarding Cost
>>
References
Cummings,
J.B., C. Withers, L. Gu, J. McIlvaine, J. Sonne, P. Fairey,
M. Lombardi, 2002. Field Testing and Computer Modeling to
Characterize the Energy Impacts of Air Handler Leakage. FSEC-CR-1357-02,
Florida Solar Energy Center, Cocoa, Florida.
*All outside air inlets should be air tight from the outside
air intake grill to the mixing box and should be equipped with
air tight, automatic dampers with a manual override switch. |